C6097A,B PRESSURE SWITCHES
65-0237—1 6
OPERATION AND CHECKOUT
Operation
The manual reset C6097A diaphragm actuates the snap-
acting switch to break a control circuit and lock out when
pressure falls to the scale setting. The recycle C6097A
models recycle automatically when the control circuit returns
to scale setting plus differential.
The manual reset C6097B diaphragm actuates the snap-
acting switch that breaks a control circuit and locks out when
the pressure rises to the scale setting. The recycle C6097B
models recycle automatically when the control pressure falls
to the scale setting minus differential.
Manual Resetting
The C6097A manual reset models lock out when pressure
falls to the scale setting and require manual resetting after the
pressure rises to scale setting plus differential to resume
normal operation.
The C6097B manual reset models lock out when pressure
rises to the scale setting and require manual resetting after
the pressure falls to scale setting minus the differential to
resume normal operation.
To reset, once normal operating pressure is restored, push the
reset button in as far as it goes, then release.
IMPORTANT
Lockout models cannot be made to recycle
automatically by permanently holding in the reset
lever.
Checkout
C6097 Gas Fuel Application
1.
Set cutoff pressure.
2.
Open main supply line. Depress reset lever on lockout
models until switch makes control circuit.
3.
Set controller and limit switch to call for heat.
4.
For C6097A: Close the manual gas shutoff valve.
C6097 should open control circuit when pressure
reaches cutoff point.
For C6097B: Open the manual gas shutoff valve, wait a
few minutes for the pressure to rise; then lower the
scale setting until the switch breaks control circuit and
locks out.
5.
For C6097A: Open the shutoff valve, return the
pressure switch to its original setting and press the reset
button (if necessary).
For C6097B: raise setting to normal and press reset
button (if necessary).
6.
Allow system to operate through at least one complete
cycle to make sure all components are functioning
properly.
C6097A Air Application
1.
Set cutoff pressure.
2.
Turn on fan.
3.
Block fan inlet or filter area. Switch should break control
circuit when pressure drops to cutoff point. Manual reset
models lock out.
4.
Remove obstruction. Press reset lever (manual reset
models) and allow system to operate through at least
one complete cycle to be sure all components are
functioning properly.