PRO-2200 Two Reader Module Installation Manual Part Number: PRO22R2 A division of Northern Computers, Inc.
PRO-2200 Two Reader Module PRO22R2 Installation Guide 3 Contents Warnings and Cautions ........................................................................................ 4 Disclaimer........................................................................................................... 6 Product Liability; Mutual Indemnification................................................................ 6 Unpacking Procedure ...................................................................................
Installation Guide PRO-2200 Two Reader Module PRO22R2 Warnings and Cautions WARNING Before installation, TURN OFF the external circuit breaker which supplies power to the system. Before connecting the device to the power supply, verify that the output voltage is within specifications of the power supply. Do not apply power to the system until after the installation has been completed.
PRO-2200 Two Reader Module PRO22R2 Installation Guide 5 CAUTION IF ANY DAMAGE TO THE SHIPMENT IS NOTICED, A CLAIM MUST BE FILED WITH THE COMMERCIAL CARRIER RESPONSIBLE. CAUTION Electro-static discharge can damage CMOS integrated circuits and modules. To prevent damage always follow these procedures: Use static shield packaging and containers to transport all electronic components, including completed reader assemblies. Handle all ESD sensitive components at an approved static controlled workstation.
Installation Guide PRO-2200 Two Reader Module PRO22R2 Disclaimer Product Liability; Mutual Indemnification In the event that a Customer receives a claim that a Product or any component thereof has caused personal injury or damage to property of others, Customer shall immediately notify Engineered Systems in writing of all such claims.
PRO-2200 Two Reader Module PRO22R2 Installation Guide 7 Shipping Instructions To ship equipment back to Engineered Systems: 1. Contact the customer service department before returning equipment at 800-323-4576. When calling, please have available: • A description of the problem or reason for returning the equipment. • Original purchase order number, invoice number and if the unit is under warranty. • A new purchase order number if the unit is not under warranty 2.
Installation Guide PRO-2200 Two Reader Module PRO22R2 Confidentiality All software, drawings, diagrams, specifications, catalogs, literature, manuals and other materials furnished by Engineered Systems relating to the design, use and service of the Products shall remain confidential and shall constitute proprietary rights of Engineered Systems and Customer agrees to treat such information as confidential.
PRO-2200 Two Reader Module PRO22R2 Installation Guide 9 Description The Two Reader Board provides support for up to two access control doors by providing connections for Wiegand or Clock/Data type readers, supervised inputs and relay outputs. This board can be rack mounted, in which case, only one edge is accessible for wiring. Mounting the board flat increases the amount of available I/O slightly but also significantly decreases the number of boards that can be mounted in one enclosure.
Installation Guide PRO-2200 Two Reader Module PRO22R2 Dipswitch Settings: S8 S7 OFF S6 OFF S5 S4 S3 S2 OFF OFF OFF OFF ON S1 ADDRESS 1* SELECTION OFF OFF OFF ON OFF ADDRESS 2 OFF OFF OFF ON ON ADDRESS 3 OFF OFF ON OFF OFF ADDRESS 4 OFF OFF ON OFF ON ADDRESS 5 OFF OFF ON ON OFF ADDRESS 6 OFF OFF ON ON ON ADDRESS 7 OFF ON OFF OFF OFF ADDRESS 8 Reserved OFF ON 9,600 BPS ON OFF 19,200 BPS ON ON OFF * = Default 38,400 BPS* Not Used*
PRO-2200 Two Reader Module PRO22R2 11 Installation Guide LED Operation The Reader board uses two on-board LEDs D79 & D80 to provide status information during its Power-up sequence as well as normal operation. MODE Power-up Sequence LED D79 LED D80 DESCRIPTION ON OFF Start Power-up, hardware setup OFF ON Testing RAM ON ON Testing ROM and completing initialization FLASH ON LED D79 flashes 4 times after Power-up is completed This is the processor heart-beat LED.
Installation Guide PRO-2200 Two Reader Module PRO22R2 For Wiring to an RS-485 port: 1. TR+ is the plus side of the transmit and receive differential signal. 2. TR- is the negative side of the transmit and receive differential signal. 3. GND is the signal ground. The wiring for this signal is required and NOT optional. This signal must NOT be connected to chassis GND. 4. Use 24 AWG low capacitance, two twisted-pair, shielded cable (Belden 9842 or equivalent).
PRO-2200 Two Reader Module PRO22R2 13 Installation Guide Single Wire Reader LED Control Configuration LED Output-> High Tri-Stated Low Single Color LED LED On LED Off LED Off Bi-Color LED Green LED On Both LEDs Off Red LED On To fully utilize each reader port, a 6-conductor cable (18AWG) is required. Reader port configuration is set via host software.
Installation Guide PRO-2200 Two Reader Module PRO22R2 Relays 1 and 3 are rated for and normally used to control the door locks associated with readers 1 and 2 respectively. While Relays 1 and 3 are sized to handle the typical loads generated by electrical locks, load switching can cause abnormal contact wear and premature contact failure. Switching of inductive loads (i.e., strike) also causes EMI (electromagnetic interference) which may interfere with normal operation of other equipment.
PRO-2200 Two Reader Module PRO22R2 Installation Guide 15 5. Connect wiring to alarm input sensors or install jumper wire as appropriate. 6. Connect relay output wiring as appropriate. 7. Connect communications wiring to the Intelligent Controller. 8. Recheck wiring for correct connections and continuity. 9. When all boards have been installed, connect the Power Supply Cord for proper connections and power. 10. Setup the panel controls using the host software.
Installation Guide PRO-2200 Two Reader Module PRO22R2 Wiring Diagram for Connectors 1 through 7 Input 5 Door EOL Status Switch RED BLACK WHITE Input 5 Common Input 6 Egress Push-Button Switch GREEN Input 6 Common EOL Typical Connection Input 1 Input 1 Common Input 2 RED Input 2 Common S-4 Suppressor Door Lock BLACK Separate Power VDC Supply + KP-13 Weigand Keypad NC RED BROWN YELLOW +5 or +12V DC Out Red LED Beeper WHITE GREEN Data-1 Data-0 BLACK Common DRAIN Chassis GND Inside
PRO-2200 Two Reader Module PRO22R2 Installation Guide 17 Wiring Diagram for Connectors 6 through 10 Note: For N-485 Communication Connections, twist the blue pair together and use as the common; use the orange pair as your data pair, observing polarity. Connect the external drain shield to the appropriate earth ground on one end.
Installation Guide NOTES PRO-2200 Two Reader Module PRO22R2