Install Instructions
INSTALLATION INSTRUCTIONS
Put Bar Code Here
62-0327-03
H7625A, H7635A, H7626A, H7636A Series
2000 Humidity/Temperature Sensors
WALL-MOUNT MODELS
APPLICATION
The H7625A, H7626A, H7635A and H7636A Wall-Mount
Humidity/Temperature Sensors are universal Relative
Humidity transmitters that can be powered with either a +18 to
40 Vdc or 24 Vac supply. The devices are half wave rectified.
The transmitter also includes either a 20K ohm NTC
thermistor or a 1K platinum PTC (compatible with the T775)
for optional temperature use.
The humidity sensors are designed with a field selectable 4 to
20 mA, 0 to 5 Vdc, or 0 to 10 Vdc output signal equivalent to 0
to 100% RH. All units are shipped from the factory with a
default setting to accept AC power with three-wire, 0 to 10 Vdc
output.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
CAUTION
Equipment Damage Hazard.
Improper wiring can damage the sensor beyond
repair.
Follow the wiring instructions carefully.
Location
Install the device where it cannot be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall behind
the device.
Mounting
The housing base mounts over standard 2 in. x 4 in. single
gang junction box or flush to the wall:
1. Install the sensor about 5 ft (1.5m) above the floor in an
area with good air circulation at average humidity and
temperature. (See Fig. 1.)
2. Ensure the device receives adequate airflow.
3. Wire the device. (See Fig. 5 through 4.)
4. Ensure proper DIP switch settings.
5. Apply power to the unit.
6. Snap the cover into position.
7. Turn out the 1/16 in. allen screws at the bottom of the
enclosure until the cover cannot be removed.
Fig. 1. Typical sensor location.
5 FEET
(1.5 METERS)
YES
NO
NO
NO
M4823A