Vents
High Pressure Steam Vent
Model 8C Angle Part No. 402002
High Pressure Balanced Pressure Air Valve
• Thermostatic vent (no float)
• Install at the high point in piping or on equipment to
quickly vent air from the steam space.
• Discharge may be piped to a safe area or into vented
return line.
•
1
/4" (6mm) orifice
• Inlet
1
/2" NPT male union connection
• Outlet
1
/2" NPT female
• Bronze body and cap
• Stainless steel element
• Maximum operating pressure 125 psig (8.6 bar)
Model 8C Angle
1
/2" NPT
B
A
NPT
Model Pattern Size AB
8C-2 Angle
1
/2 2
27
/32 (72) 1
1
/4 (32)
Dimensions, in. (mm)
Air make up coil with F&T Float & Thermostatic trap
draining into a wet return line
Note: A separate thermostatic trap is added to vent air into
the dry return line.
Dry return line
Wet return line
Thermostatic
Trap
F&T
Trap
Hoffman Specialty
®