Brochure

57
Regulators
Hoffman Specialty
®
Regulators
Inlet Pressure Weight
Model Part Operating Operating (Approx.)
Number Number Mode Range psig (bar) lbs. (kg)
SLD-100 402247 Normally Open 0-100 (0-6.9) 1
1
/2 (.68)
SLD-250 402259 Normally Open 0-250 (0-17.3) 6 (2.7)
SLD-100 402255 Normally Closed 0-100 (0-6.9) 1
1
/2 (.68)
SLD-250 402258 Normally Closed 0-250 (0-17.3) 6 (2.7)
Series SLD Solenoid Pilots
Solenoid Pilot
Model SLD-100
Solenoid Pilot
Model SLD-250
Ordering Information
1
7
/8"
(12mm)
3
5
/16"
(84mm)
1
/4"
NPT
2
3
/4"
(70mm)
8
1
/8"
(206mm)
7
1
/4"
(184mm)
2
11
/16"
(68mm)
1
/4"
NPT
Solenoid pilots are used with other pilots for overrides in
domestic hot water or safety applications. The “Normally
Closed” Solenoid pilots are designed to shut down the
Main valve if there is a power failure. “Normally Open”
Solenoid pilots are designed for heating, or other
applications where overheating will not be harmful, since
they remain open during a power failure.
Remote control
Emergency shut-down feature
Automatic start-up and shut-down capability (timer required)
More economical to use than electric shut-off valves
Operating modes
– Normally Open
– Normally Closed
120 volt electrical service required
Maximum operating pressure 250 psig (17.3 bar)
Do not use “Normally Open” Solenoid
pilots for direct temperature control in
domestic water applications.
Failure to follow this warning can cause
serious burns, personal injury, or death.
!