Brochure

21
Hoffman Specialty
®
Steam Traps
Steam Traps
Dimensions, in. (mm)
Series 17C Balanced Pressure
®
Gross Ratings
Series 17C capacities are based on 40˚ F (22˚C) subcooling. Cold capacity is approximately 4 times capacity shown.
Differential Across Trap psi
1
4
1
2
11
1
2
2 5 10 15 25
Series Capacity sq. ft. EDR
*
17C 85 120 165 200 235 370 530 640 800
SHEMA
* Ratings are in accordance with recommended standards established by the
Steam Heating Equipment Manufacturers association (SHEMA).
1 sq. ft. EDR is equivalent to a heat emission of 240 BTU per hour with 2 psig
steam filling a radiator surrounded by 70˚F ambient air.
To convert sq. ft. EDR to lbs. of condensate, or steam per hour, divide the sq. ft.
rating by 4.
Ordering Information
Differential Across Trap psi (bar)
1
4
1
2
11
1
2
2 5 10 15 25
(.017) (.034) (.069) (.10) (.14) (.35) (.7) (1.0) (1.7)
Series
Capacity lb/hr (kg/hr)
17C
42 51 63 72 77 102 125 140 162
(19) (23) (29) (33) (35) (46) (57) (64) (73)
Differential
NPT BSPT NPT BSPT Pressure
Model Model Size Part Part
Rating Weight
Number Number in. Number Number psi (bar) lbs. (kg)
17C-AS-2-25 Angle (w/short nipple)
1
2 401542 25 (1.7) 1.2 (.54)
17C-A 2-25 Angle
1
2 401536 25 (1.7) 1.2 (.54)
17C-V 2-25 Vertical
1
2 401551 25 (1.7) 1.2 (.54)
17C-SV-2-25 Swivel
1
2 401545 25 (1.7) 1.2 (.54)
17C-A-3-25 Angle 17C-A-3J-25 Angle
3
4 402006 402014 25 (1.7) 1.5 (.7)
17C-S-3-25 Straightaway
3
4 402011 25 (1.7) 1.3 (.6)
17C-A-4-25 Angle 1 402012 25 (1.7) 2.3 (1)
Size
Model Pattern in. A BC
17C-AS-2-25 Angle (w/short Nipple)
1
2 2
27
32 (72) 1
1
4 (32)
17C-A-2-25 Angle
1
2 3
1
4 (83) 1
1
4 (32)
17C-V-2-25 Vertical
1
2 4
23
32 (120) —2
1
8 (54)
17C-SV-2-25 Swivel
1
2 3
1
4 (83)
15
16 (24) 1
13
16 (46)
17C-A-3-25 Angle
3
4 3
1
8 (79) 1
1
2 (38)
17C-S-3-25 Straightaway
3
4 3
5
32 (80) 1
1
8 (29) 1
5
8 (41)
17C-A-4-25 Angle 13
7
32 (82) 1
3
4 (45)