Instruction Manual INVERTER SJ700-2

Chapter 8 List of Data Settings
8 - 13
Default
Code Function name Monitored data or setting
_FF _FEF _FUF
Setting
during
operation
(allowed or
not)
Change
during
operation
(allowed or
not)
Page
H001 Auto-tuning Setting
00 (disabling auto-tuning), 01 (auto-tuning without rotation), 02 (auto-tuning
with rotation)
00
¯ ¯
H002 Motor data selection, 1st motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
¯ ¯
H202 Motor data selection, 2nd motor
00 (Hitachi standard data), 01 (auto-tuned data),
02 (auto-tuned data [with online auto-tuning function])
00
¯ ¯
H003 Motor capacity, 1st motor 0.20 to 75.00 (kW) Factory setting
¯ ¯
H203 Motor capacity, 2nd motor 0.20 to 75.00 (kW) Factory setting
¯ ¯
H004 Motor poles setting, 1st motor 2, 4, 6, 8, 10 (poles) 4
¯ ¯
H204 Motor poles setting, 2nd motor 2, 4, 6, 8, 10 (poles) 4
¯ ¯
4-85
H005 Motor speed constant, 1st motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1.590
{ {
H205 Motor speed constant, 2nd motor 0.001 to 9.999, 10.00 to 80.00 (10.000 to 80.000) 1.590
{ {
4-89
H006
Motor stabilization constant, 1st
motor
0. to 255. 100.
{ {
H206
Motor stabilization constant, 2nd
motor
0. to 255. 100.
{ {
H306
Motor stabilization constant, 3rd
motor
0. to 255. 100.
{ {
4-79
H020 Motor constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H220 Motor constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H221 Motor constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H221 Motor constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H222 Motor constant L, 1st motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
¯ ¯
H222 Motor constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
¯ ¯
H223 Motor constant Io 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
¯ ¯
H223 Motor constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
¯ ¯
H224 Motor constant J 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
¯ ¯
H224 Motor constant J, 2nd motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
¯ ¯
4-88
H030 Auto constant R1, 1st motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H230 Auto constant R1, 2nd motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H231 Auto constant R2, 1st motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H231 Auto constant R2, 2nd motor
0.001 to 9.999, 10.00 to 65.53 ()
Depending on motor capacity
¯ ¯
H232 Auto constant L, 1st motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
¯ ¯
H232 Auto constant L, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (mH) Depending on motor capacity
¯ ¯
H233 Auto constant Io, 1st motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
¯ ¯
H233 Auto constant Io, 2nd motor 0.01 to 99.99, 100.0 to 655.3 (A) Depending on motor capacity
¯ ¯
H234 Auto constant J, 1st motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
¯ ¯
Control constants
H234 Auto constant J, 2nd motor 0.001 to 9.999, 10.00 to 99.99, 100.0 to 999.9, 1000. to 9999. Depending on motor capacity
¯ ¯
4-85