Fault Codes DTC & Troubleshooting

Table Of Contents
2 TROUBLESHOOTING
- 45 -
The load is turned on of off irregularly.
Check if: What to do
The external load power voltage is too low. If true, raise it.
Adequate noise reduction measures are taken. Use surge absorbers.
Take measures to protect the laid
cables from any noise source.
For more information, refer to the
description under “4 HANDLING”
in the “S10mini HARDWARE
MANUAL, I/O MODULES (manual
number SME-1-114).”
Line breakage
Nonconforming
wiring length
Replace the cable
Incomplete
connection
Connect it completely.
The remote I/O cable is
abnormal.
Terminating
resistor(s)
missing
Connect them properly.
The program is error-free. If not, correct the program.