Type_approval_A-0_DNV-GL_CFS-T

Job Id: 262.1-029958-1
Certificate No: TAF0000175
Form code: TA 251 Revision: 2016-12 www.dnvgl.com Page 4 of 5
Application
Bulkhead
Frame/Sleeve
Size
min.
Frame/Sleeve
Size
max.
Minimum
filling rate
(%)
Maximum
filling rate
(%)
Coaming
position in
bulkhead
Cables-
Maximum
Diameter
(mm)
CFS-T RR 50mm Ø 200mm Ø 0 48 symmetrically,
exposed or
unexposed
47,3
CFS-T RRS 50mm Ø 100mm Ø 0 100 symmetrically,
exposed or
unexposed
25
Optional: CFS-T EMC sealing solution
Application/Limitation
Approved for use as a cable penetration system in class A-0 steel bulkheads and decks. Other
applications are subject to case-by-case approval.
Pressure tests for rectangular frames listed in tables of page 2, 3 and 4 (except EMC Modules).
Approved for air tightness up to a design pressure of 0.1 MPa (1 bar), test pressure - 0.15 MPa (1.5 bar)
Approved for water tightness up to a design pressure of 0.3 MPa (3 bar), test pressure - 0.45 MPa
(4.5 bar)
Penetration systems are not to be used for penetrating boundaries of tanks.
Each product is to be supplied with its manual for installation, use and maintenance.
Type Approval documentation
Test Reports A0 Fire Class No.:
19288A dated 2018-11-20, 19289A dated 2018-11-20, 19290A dated 2018-11-20,
19444A dated 2019-01-16, 19540A dated 2019-03-14
Installation drawings No.:
Bulkhead, dated 2019-03-11
CFS-T_SSF001, CFS-T_SS002/003/004/005,
CFS-T_SSR/R30_006 to 009, CFS-T_SSR_010 to 013,
CFS-T_RR014 to 018, CFS-T_RRS019 to 023,
Deck, dated 2019-03-15
CFS-T_SSF001/002/006-D,
CFS-T_SS003/004/005/007/008-D,
CFS-T_SSR/R30_009-D to 013-D, CFS-T_SSR_014-D to 018-D,
CFS-T_RR019-D to 026-D, CFS-T_RRS027-D to 033-D
Pressure tests: Hilti Test Report No. WGT CFS-T-291018-01 dated 2018-10-29
WGT CFS-T-070219-01 dated 2019-02-07