Full Product Manual
HearthSense
25200549-01A
TROUBLESHOOTING
Problem Possible Cause Corrective Action
Heater produces un-
wanted odors.
1.
Heater is burning vapors from
paint, hair spray, glues, etc. See
IMPORTANT statement, page 22.
2. Gas leak. See Warning State-
ment at the top of page 22.
3 Low fuel supply (propane
gas only).
1. Ventilate room. Stop using
odor causing products while
heater is running.
2. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 16).
3. Rell supply tank (Propane
models).
Heater produces a whis-
tling noise when burner
is lit.
1. Turning control knob to high
position when burner is cold.
2. Air in gas line.
3. Air passageways on heater
are blocked.
4. Dirty or partially clogged
burner orice.
1. Turn control knob to low
position and let warm up for
a minute.
2.
Operate burner until air is re-
moved from line. Have gas line
checked by local gas supplier.
3
Observe minimum installation
clearances (Figure 4, page 9).
4 Clean burner (see Care and
Maintenance, page 21).
Heater produces a click-
ing/ticking noise just after
burner is lit or shut o.
1. Metal is expanding while
heating or contracting while
cooling.
1. This is common with most
heaters. If noise is exces-
sive, contact qualied ser-
vice technician.
White powder residue
forming within burner
box or on adjacent walls
or furniture.
1. When heated, the vapors
from furniture polish, wax,
carpet cleaners, etc., turn
into white powder residue.
1. Turn heater o when using
furniture polish, wax, carpet
cleaner or similar products.
Heater shuts o in use
(ODS operates).
1. Not enough fresh air is avail-
able.
2. Low line pressure.
3. ODS/pilot is partially clogged.
1. Open window and/or door for
ventilation.
2. Contact local gas supplier.
3. Clean ODS/pilot (see Care
and Maintenance, page 21).
Gas odor exists even
when control knob is in
OFF position.
1. Gas leak. See Warning
Statement at top of page 22.
2. Control valve is defective.
1. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 16).
2. Replace control valve.
Moisture/condensation
noticed on windows.
1. Not enough combustion/
ventilation air.
1. Refer to Air for Combus-
tion and Ventilation require-
ments, page 7.
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact
ProCom Heating, Inc. at 1-866-573-0674.
When calling, please have your model and serial numbers of your heater ready.