Brochure

Table Of Contents
Technical data
UP Series
6
47
UPS 15-35 SUC/SFC
Note: If the UP pump is equipped with a timer, the
maximum liquid temperature is 150 °F (66 °C).
Approvals
Note: LC/TLC models have a 6 ft (1.8 m), 3-prong power cord. Removable check valve.
Dimensions in inches unless otherwise noted.
TM03 8850 4412
0 2 4 6 8 10 12 14 16 18 Q [US GPM]
0
1
2
3
4
5
6
7
8
9
10
11
12
[ft]
H
0 1 2 3 4 Q [m³/h]
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
[m]
H
UPS15-35
60 Hz
3
2
1
Flow range: 0-21.5 gpm (0-4.9 m
3
h)
Head range: 0-12 ft (0-3.7 m)
Motors: 2-pole, single-phase
Max. liquid temperature: 165 °F (74 °C)
Min. liquid temperature: 36 °F (2 °C)
Max. system pressure: 145 psi (10 bar)
Model Speed Volts Amps Watts Hp Capacitor
UPS 15-35 SUC/
SFC
3
115
0.95 110 0.15
10 μF/180 V20.75840.11
1 0.55 61 0.08
Without check valve
With check valve
UPS 15-35 SFC UPS 15-35 SUC/TLC
TM03 8779 2507
TM03 8778 2507
Model
Product
number
115 V
Dimensions [inches (mm)]
Connection
type and size
Shipping
weight
[lbs (kg)]
ABCDEF
UPS 15-35 SFC 59896772 6.50 (165) 5.50 (140) 4.13 (105) 3.88 (99) 2.94 (75) 3.13 (80) GF 15/26 6.0 (2.7)
UPS 15-35 SUC 59896778 5.88 (149) 5.06 (129) 4.13 (105) 3.44 (87) 2.934 (75) - GU 125 5.4 (2.5)
UPS 15-35 SUC/TLC 59896780 5.88 (149) 5.06 (129) 4.13 (105) 3.44 (87) 2.934 (75) - GU 125 6.2 (2.8)