Specifications
Table Of Contents
2 www.goodmanmfg.com SS-DSXC18
SS-DSXC18 www.goodmanmfg.com 3
Product Specifications
DSXC18
0361A
DSXC18
0481A
DSXC18
0601A
Nominal Cooling (BTU/h) 35,000 47,000 57,000
Decibels 71 72 74
RLA 15.3 21.2 27.1
LRA 83 104 152.9
Horsepower (RPM) ⅓ ⅓ ⅓
FLA 2.80 2.80 2.80
Refrigerant Line Size¹
Liquid Line Size (“O.D.) ⅜" ⅜" ⅜"
Sucon Line Size (“O.D.) ⅞" 1⅛" 1⅛"
Refrigerant Connecon Size
Liquid Valve Size (“O.D.) ⅜" ⅜" ⅜"
Sucon Valve Size (“O.D.) ⅞" ⅞" ⅞"
Valve Connecon Type Sweat Sweat Sweat
Refrigerant Charge 184 259 259
Expansion Device TXV TXV TXV
Superheat at Service Valve 7-9°F 7-9°F 7-9°F
Subcooling at Service Valve 5-7°F 5-7°F 5-7°F
Voltage-Phase-Hz 208/230-1-60 208/230-1-60 208/230-1-60
Minimum Circuit Ampacity ¹ 21.9 29.3 36.7
Max. Overcurrent Protecon ² 35 50 60
Min / Max Volts 197 / 253 197 / 253 197 / 253
Electrical Conduit Size ½" or ¾" ½" or ¾" ½" or ¾"
206 268 274
228 290 296
ENERGY STAR®
NO
• Proper sizing and installaon of equipment is crical to achieving opmal performance. Split system air condioners and
heat pumps must be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your contractor for
details or visit www.energystar.gov.
• The www.energystar.gov website provides up-to-date system combinaons cered to meet ENERGY STAR requirements.
• See Page 16 for all ENERGY STAR cered combinaons as of this document’s revision date.
¹ Wire size should be determined in accordance with Naonal Electrical Codes; extensive wire runs will require larger wire sizes
² Must use me-delay fuses or HACR-type circuit breakers of the same size as noted.
• Always check the S&R plate for electrical data on the unit being installed.
• Installer will need to supply ⅞” to 1⅛” adapters for sucon line connecons.
• Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be ad-
justed per Installaon Instrucons Final Charge Procedure.
• Installaon of these units that require a TXV Kit to be installed on the indoor coil.
• PLEASE NOTE: the specied TXV is determined by the outdoor unit, not the indoor coil.