Technical Manual

24
COOLING PERFORMANCE DATA
GSX130611A*
EXPANDED PERFORMANCE DAT
A
COOLING OPERATION
MODEL: GSX130611/CA*F4961*6D*+EEP
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 59636771596367715963677159 63 67715963677159636771
MBH 53.8 55.7 61.0 - 52.5 54.4 59.6 - 51.3 53.1 58.2 - 50.0 51.8 56.8 - 47.5 49.2 53.9 - 44.0 45.6 50.0 -
S/T 0.66 0.55 0.38 - 0.68 0.57 0.39 - 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.75 0.62 0.43 - 0.75 0.63 0.44 -
Delta T 22 19 14 - 22 19 14 - 22 19 14 - 22 19 14 - 22 19 14 - 20 18 13 -
1500 System KW 3.97 4.05 4.18 - 4.27 4.37 4.51 - 4.54 4.64 4.80 - 4.78 4.89 5.05 - 4.99 5.10 5.27 - 5.16 5.28 5.45 -
OD amps 15.4 15.8 16.3 - 16.7 17.1 17.6 - 18.1 18.6 19.2 - 19.4 19.9 20.6 - 20.7 21.2 21.9 - 22.0 22.5 23.3 -
HI PR 228 245 259 - 256 275 291 - 291 313 331 - 331 357 377 - 373 401 424 - 412 443 468 -
LO PR 98 104 114 - 103 110 120 - 107 114 125 - 113 120 131 - 118 126 137 - 122 130 142 -
MBH 55.4 57.4 62.9 - 54.1 56.1 61.4 - 52.8 54.7 59.9 - 51.5 53.4 58.5 - 48.9 50.7 55.6 - 45.3 47.0 51.5 -
S/T 0.69 0.57 0.40 - 0.71 0.60 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.44 - 0.78 0.65 0.45 - 0.79 0.66 0.46 -
Delta T 20 17 13 - 20 18 13 - 20 18 13 - 20 18 13 - 20 17 13 - 19 16 12 -
70 1750 System KW 4.00 4.09 4.21 - 4.31 4.40 4.54 - 4.58 4.68 4.84 - 4.82 4.93 5.09 - 5.03 5.14 5.31 - 5.20 5.32 5.50 -
OD amps 15.5 15.9 16.4 - 16.8 17.2 17.8 - 18.3 18.8 19.4 - 19.6 20.1 20.8 - 20.9 21.4 22.2 - 22.2 22.7 23.5 -
HI PR 230 248 262 - 258 278 294 - 294 316 334 - 335 360 380 - 377 405 428 - 416 448 473 -
LO PR 99 105 115 - 104 111 121 - 108 115 126 - 114 121 132 - 119 127 139 - 124 131 143 -
MBH 55.6 57.7 63.2 - 54.3 56.3 61.7 - 53.0 55.0 60.2 - 51.8 53.6 58.8 - 49.2 51.0 55.8 - 45.5 47.2 51.7 -
S/T 0.70 0.58 0.40 - 0.72 0.60 0.42 - 0.74 0.62 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.80 0.67 0.46 -
Delta T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
2000 System KW 4.03 4.12 4.25 - 4.34 4.44 4.58 - 4.62 4.72 4.88 - 4.86 4.97 5.13 - 5.07 5.18 5.36 - 5.25 5.37 5.55 -
OD amps 15.7 16.0 16.6 - 17.0 17.4 18.0 - 18.5 18.9 19.6 - 19.8 20.3 21.0 - 21.1 21.6 22.4 - 22.4 22.9 23.7 -
HI PR 233 250 264 - 261 281 297 - 297 319 337 - 338 364 384 - 380 409 432 - 420 452 477 -
LO PR 100 106 116 - 105 112 122 - 110 117 127 - 115 122 134 - 121 128 140 - 125 133 145 -
MBH 54.756.360.965.453.455.059.563.952.153.758.162.350.9
52.4
56.7 60.8 48.3 49.7 53.8 57.8 44.7 46.1 49.9 53.5
S/T 0.750.670.500.320.770.690.520.340.790.710.540.350.82
0.73
0.55 0.36 0.85 0.76 0.57 0.37 0.86 0.77 0.58 0.37
Delta T 25231913252319132523191326
23
19 13 25 23 19 13 23 22 18 12
1500 System KW 4.00 4.09 4.22 4.35 4.31 4.40 4.55 4.69 4.58 4.68 4.84 5.00 4.82
4.93
5.09 5.26 5.03 5.14 5.31 5.49 5.20 5.32 5.50 5.69
OD amps 15.5 15.9 16.4 17.1 16.8 17.2 17.8 18.5 18.3 18.8 19.4 20.2 19.6
20.1
20.8 21.6 20.9 21.4 22.2 23.0 22.2 22.7 23.5 24.4
HI PR 230 248 262 273 258 278 294 306 294 316 334 348 335
360
380 397 377 405 428 446 416 448 473 493
LO PR 99 105 115 122 104 111 121 129 108 115 126 134 114
121
132 141 119 127 139 148 124 131 143 153
MBH 56.358.062.767.355.056.661.365.853.755.359.864.252.4
53.9
58.4 62.6 49.8 51.2 55.5 59.5 46.1 47.5 51.4 55.1
S/T 0.780.700.530.340.810.720.550.350.830.740.560.360.86
0.77
0.58 0.37 0.89 0.80 0.60 0.39 0.90 0.80 0.61 0.39
Delta T 23211712232218122322181224
22
18 12 23 21 18 12 22 20 16 11
75 1750 System KW 4.03 4.12 4.25 4.39 4.34 4.44 4.58 4.73 4.62 4.72 4.88 5.04 4.86
4.97
5.14 5.31 5.07 5.18 5.36 5.54 5.25 5.37 5.55 5.74
OD amps 15.7 16.1 16.6 17.2 17.0 17.4 18.0 18.7 18.5 18.9 19.6 20.3 19.8
20.3
21.0 21.8 21.1 21.6 22.4 23.2 22.4 22.9 23.7 24.7
HI PR 233 250 264 276 261 281 297 309 297 320 337 352 338
364
384 401 380 409 432 451 420 452 478 498
LO PR 100 106 116 123 105 112 122 130 110 117 127 136 115
122
134 142 121 128 140 149 125 133 145 154
MBH 56.658.363.167.755.356.961.666.153.955.560.164.552.6
54.2
58.7 63.0 50.0 51.5 55.7 59.8 46.3 47.7 51.6 55.4
S/T 0.790.710.540.350.820.730.560.360.840.750.570.370.87
0.78
0.59 0.38 0.90 0.81 0.61 0.39 0.91 0.81 0.62 0.40
Delta T 21191611211916112119161121
19
16 11 21 19 16 11 19 18 15 10
2000 System KW 4.06 4.15 4.28 4.42 4.38 4.48 4.62 4.77 4.66 4.76 4.92 5.08 4.90
5.01
5.18 5.35 5.11 5.23 5.40 5.59 5.29 5.41 5.59 5.78
OD amps 15.8 16.2 16.7 17.4 17.1 17.6 18.1 18.8 18.7 19.1 19.8 20.5 20.0
20.5
21.2 22.0 21.3 21.8 22.6 23.5 22.6 23.2 24.0 24.9
HI PR 235 253 267 278 264 284 300 312 300 323 341 355 341
367
388 405 384 413 437 455 424 457 482 503
LO PR 101 107 117 125 106 113 124 132 111 118 129 137 116
124
135 144 122 130 141 151 126 134 146 156
* Entering Indoor Dry Bulb Temperature NOTE: Shaded area is ACCA (TVA) conditions AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves. KW=Total system power