Specification

NOV 2016 GFS-100b (Formerly A-65)
STANDARD RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
TECHNICAL DATA
See reverse side for Approvals and Speci cations.
Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C)
500°F (260°C) Available Upon Request Without Approvals
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze De ector - brass Screw - brass
Lodgement Wire - stainless steel Bulb seat - copper
Spring - nickel alloy Seal - te onw
Bulb - glass with glycerin solution, 5mm size
Escutcheon Assembly - steel
DESCRIPTION AND OPERATION
CLASSIFICATION
AVAILABLE SPRINKLER
TEMPERATURES
BULB COLOR
N.F.P.A. MAXIMUM
CEILING TEMPERATURE
ORDINARY
INTERMEDIATE
HIGH
EXTRA HIGH
ULTRA HIGH
135°F/155°F
175°F/200°F
286°F
360°F
500°F
57°C/68°C
79°C/93°C
141°C
182°C
260°C
ORANGE/RED
YELLOW/GREEN
BLUE
MAUVE
BLACK
100°F
150°F
225°F
300°F
475°F
38°C
66°C
107°C
149°C
246°C
UPRIGHT CONVENTIONAL
PENDENT VERTICAL
SIDEWALL
STANDARD RESPONSE
HORIZONTAL
SIDEWALL
LPC/CE
HORIZONTAL
SIDEWALL
STANDARD RESPONSE
STANDARD RESPONSE
The Globe Standard Response GL Series Sprinklers are a low
pro le yet durable design which utilizes a 5mm frangible glass
ampule as the thermosensitive element. While the Standard
Response Sprinkler provides an aesthetically pleasing appear-
ance, it can be installed wherever standard spray sprinklers are
speci ed when allowed by the applicable standards. It offers
the additional feature of greatly increased safety to life and is
available in various styles, ori ces, temperature ratings and n-
ishes to meet varying design requirements. Standard Response
Sprinklers should be used advisedly and under the direction of
approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that
contains a precisely measured amount of uid. When heat is
absorbed, the liquid within the bulb expands increasing the
internal pressure. At the prescribed temperature the internal
pressure within the ampule exceeds the strength of the glass
causing the glass to shatter. This results in water discharge which is
distributed in an approved pattern depending upon the de ector
style used.
The sprinkler and escutcheon are not factory assembled.
Assembly is done in the eld.

Summary of content (2 pages)