Install Instructions

1
F O R M
Evergreen
®
VS Motor
Installation Guide
G0076E
Revised
June 2019
Regal Beloit America, Inc.
1325 Heil Quaker Blvd.
LaVergne, TN 37086
Customer Service: 800 672 6495
thedealertoolbox.com
www.regalbeloit.com
CAUTION indicates a hazardous situation that, if not avoided,
could result in minor or moderate injury.
Periodic inspections should be performed. Failure to perform
proper maintenance could result in premature product failure.
Installation and service of this Evergreen VS user interface and
motor should be performed only by trained service technicians
familiar with these products.
This Evergreen VS user interface and motor should be
installed in accordance with accepted practices and installation
instructions, and in compliance with all national and local codes.
WARNING indicates a hazardous situation that, if not avoided, could
result in death or serious injury.
Read and follow all instructions carefully.
Disconnect and lock out the main power from the unit being
serviced before installing the Evergreen VS user interface and
motor. It is also a good practice to confirm that the power is
disconnected with a voltmeter.
Do not operate equipment without guards in place.
Improper installation, adjustment, alteration, service,
maintenance, or use could cause explosion, fire, electrical shock,
or other conditions. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance.
The qualified installer or agency must use the supplied or
recommended parts when installing or servicing this product.
After installing the Evergreen
®
VS motor, it is the responsibility
of the installing technician to verify the HVAC system matches
the manufacturers requirements for proper operation, capacity,
efficiency and safety.
Genteq ECM model 3.0 motor
Genteq Evergreen VS motor
INTRODUCTION
The Evergreen VS motor is designed to replace Genteq
®
constant airflow (variable speed) ECM model 3.0 motors. This includes ECM
indoor blower motors made by Regal and its predecessor manufacturer and sold under other Regal and predecessor manufacturer
brands. The Evergreen VS motor is a constant airflow (variable speed) motor. It will operate in constant airflow mode when it is
receiving digital serial interface (DSI) and constant torque mode when it is receiving pulse width modulation (PWM) communication.
NOTE: Evergreen VS user interface (5K010) is required for replacing Genteq model 2.3 or Eon
®
motors built
with a16-pin communication plug.
APPLICATIONS - GENTEQ 3.0 MOTORS ONLY
The Evergreen VS motor is designed for use in the following types of HVAC systems:
Furnace, air handler and package units
Fossil fuel, electric strip heat, A/C, heat pump and geothermal units
Single stage, multi-stage, modulating and communicating systems
Replacing a Genteq model 3.0 motor (4-pin communication plug):
Install one (1) Evergreen VS motor
o For proper replacement of the Genteq ECM model 3.0 motors, match the horsepower (HP)
and voltage (VAC) ratings of the new Evergreen VS motor to the motor being replaced. It is
not necessary for the RPM or the amperage (FLA) to match.
Stock # 6503V 1/3 HP 120/240 VAC CCW/CW
Stock # 6505V 1/2 HP 120/240 VAC CCW/CW
Stock # 6507V 3/4 HP 120/240 VAC CCW/CW
Stock # 6510V 1 HP 120/240 VAC CCW/CW
All Evergreen VS motors are dual rotation (established by communication) and dual voltage
(established by the OEM harness).
REMOVAL AND INSTALLATION OF THE MOTOR
Remove the old motor
1. Turn off the main line voltage disconnect to the HVAC system.
2. Unplug the 5-pin line voltage plug and the 4-pin communication plug from the ECM Model 3.0
motor.
3. Remove the old motor from the blower section. Leave the belly band mount connected to the
blower section.

Summary of content (2 pages)