Product Manual

General Information
4 Homelink Upgradeable Manual Transfer Switch Owner’s Manual
Power Inlet Box (if equipped)
The Power Inlet Box (PIB) safely connects a portable
generator to the manual transfer switch.
Two types of enclosure are available:
Corrosion-resistant aluminum
Non-metallic resin
The conductor size range is as follows:
Safe Use of Transfer Switch
Before installing, operating or servicing this equipment,
read the Safety Rules carefully. Comply strictly with all
Safety Rules to prevent accidents and/or damage to the
equipment. The manufacturer recommends that a copy
of the Safety Rules be posted near the transfer switch.
Also, be sure to read all instructions and information
found on tags, labels and decals affixed to the
equipment.
Publications that outline the safe installation and
manufacturing of transfer switches are the following:
NFPA 70; National Electrical Code
UL 1008, STANDARD FOR SAFETY-AUTOMATIC
TRANSFER SWITCHES
UL67 Panel boards
NOTE: To ensure code compliance, it is essential to use
the latest version of any standard that has been adapted
by your local municipality.
Load Management Options
Loads can be managed using a smart power
management system. The system can accommodate up
to eight individual Smart Management Modules (SMM).*
NOTE: SMMSs are self-contained and have individual
built-in controllers.
*See SMM Module (available separately)
PIB
Rating
Wire Range Conductor
Tightening
Tor q ue
Lug Temp.
Rating
30A
50A
8 - 14 AWG
50 in-lbs
(5.6 Nm)
167°F (75°C)
(000100a)
WARNING
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.