Installation Instructions

GEI M1010-A
© Copyright 2011 General Electric Company
6
3. For direct coupled applications use flexible couplings if possible.
Accurate mechanical lineup is essential for successful operation. Mechanical vibration and roughness in
running the motor may be an indication of poor alignment. In general, lineup by straight edge across,
and feeler gauges between coupling halves is not sufficiently accurate. It is recommended that the
lineup be checked with a dial indictor and checking bars connected to the motor and load-machine
shafts. The space between coupling hubs should be maintained as recommended by the coupling
manufacturer. Shaft offset should not exceed 0.002”. Angular misalignment should be less than 0.002”.
4. The application of pulleys, sheaves, sprockets, and gears on the motor’s shaft is shown in NEMA Standard
MG1-14.07. The application of the V-belts dimensions for alternating current motors is in MG1-14.42. V-
belt sheave pitch diameters should not be less than the values shown in Table 14-1 of NEMA MG-1.
Sheave ratios greater than 5:1 and center-to-center distances less than the diameter of the large sheave
should be referred to the Company. Make certain that the minimum allowed diameter of the motor
pulley and the maximum belt tension are not exceed because an excessive pull may cause bearing
trouble and shaft failures. Tighten belts only enough to prevent slippage. Belt speeds should not exceed
5000 feet per minute (25 meters per second). When V-belts are used, sheave ratios greater than 5:1 and
center-to-center distances less than the large sheave shall not be used. The dimensions of the belt pulley
are to be determined according to the kind of belt, transmission and capacity to be transmitted. Vent
holes have to be kept free and required minimum distances are to be observed in order not to obstruct
the flow of cooling air. In addition, make sure that the discharged hot air is not re-circulated into the
motor.
C. Power Supply and Connections
1. Nameplate voltage and frequency should agree with the power supply. Motors will operate satisfactorily
on line voltage within ±10% of the nameplate value or frequency within ±5%, combined variation not to
exceed ±10%.
2. Dual voltage motors can be connected for the desired voltage using instructions on the nameplate or the
connection diagram.
3. Wiring of motor, control, overload protection and grounding should meet the National and Local codes.
4. When mounting conditions permit, the conduit box may be rotated so that the conduit entrance can be
made upward, downward, or from either side. For oversize conduit boxes, the mounting height of the
motor may have to be increased for accessibility.
WARNING: Motor and control overload protection and grounding should be in accordance with
the USA -National Electric Code’ orBS/EN 60204-1’ and/or ‘BS/EN 60204-11’ and consistent with
sound local practices.
IV. OPERATION
A. Steps Prior to Starting
WARNING: If the motor has been in a damp location, dry it out thoroughly before operating.
Before energizing the motor for the first time or after an extended shut down, it is advisable to
check the insulation resistance, power supply and mechanical freedom of the motor.
In accordance with established standards, the recommended minimum insulation resistance for the stator winding
when measured with a 500 volt DC direct indicating ohmmeter with self-contained power supply (megger), shall not
be less than 5 mega-ohms at 40°C for a motor rated under 1000 volts, and not less than 100 mega-ohms at 40°C for
a motor rated over 1000 volts. If the insulation resistance is lower than this value, it is advisable to eliminate the
moisture in one of the following ways.