Manual

Installation
Checklist Electric shock hazard.
Turn off electric power before service or installaSor
All electrical connections and circuits are installed in compli-
ance with and conform to the National Electrical Code and lo-
cal codes which have jurisdiction.
_/ Wall sleeve and condensate lines are installed correctly.
_/ Electrical power is disconnected.
_/ Condenser air inlet and outlet MUST be clear and free of obstructions.
_/ Cardboard wall sleeve support and louver weatherboard are removed.
_/ Wall sleeve foam gasket is installed (if applicable).
_/ Subbase kit or other means of structural support is required for ALL installations which project more than 8"
into room.
_/ Unit is installed in a 16"H x42"Wx 11 1/2"D wall sleeve. A sleeve baffle kit is used when installed in a sleeve
greater than 11 1/2" deep.
_/ Ensure that drapes, bed, bedspread, furniture, etc. DO NOT block either return or discharge air louvers.
_/ Condensate Drain Kits should be installed for complete condensate removal.
Read these instructions carefully and completely
before attempting installation. Unit should be
installed by qualified service personnel ONLY.
Failure to do so can result in property damage,
personal injury and/or death.
Wire Size
Fuse/Circuit
Breaker
Grounding
Receptacle
Wire Sizing
Electrical
Requirements
Use ON LY wiring size recommended for single out-
let branch circuit.
Use ONLY type and size fuse or HACR circuit
breaker.
Electric shock hazard.
Turn OFF electric power before service or installation.
All electrical connections and wiring MUST be installed
by a qualified electrician and conform to the National
Electrical Code and all local codes which have juris-
diction.
Failure to do so can result in property damage, per-
sonal injury and/or death.
Indicated on unit's rating plate (see page 4). Proper current protection to the unit is the responsibility of
the owner. NOTE: A time delay fuse is provided with 265V units.
Unit MUST be grounded from branch circuit through service cord to unit, or through separate ground
wire provided on permanently connected units. Be sure that branch circuit or general purpose outlet is
grounded.
The field supplied outlet must match plug on service cord and be within reach of service cord. Refer to
Table 1 for proper receptacle and fuse type. Do NOT alter the service cord or plug. Do NOT use an
extension cord.
Use recommended wire size given in Table 2 and install a single branch circuit. All wiring must comply
with local and national codes. NOTE: Use copper conductors only.
rl'l