Accessory Installation Manual (2022)
A
B
C
D F
I
H
J
K
E
SINGLE LAMP GERMICIDAL
UV LIGHT KIT
INSTALLATION GUIDE
MODEL UVT1 is installed inside PTACs, Vert-I-Pak, VRP, fan coils, and air handlers with limited
access to reduce biological contamination for reduced system maintenance and improved
indoor air quality.
1
Installation in PTACs models PZ, PH, PE
US patent #7,704,463FRIE-UVT1-MAN 021721
Parts Included
A
UV Lamp, Shield & Pig Tail
“ST” Power Supply
B
Self -Tapping Screws
C
Spade Connectors
D
Piggyback Terminal Connectors
E
Sight Glass
F
O-Ring Lamp Retainers
G
Zip-Tie Base
H
Split-Loom Protector
I
Warning Sticker
J
Zip-Tie
K
L
IMPORTANT!
• Install so that direct UV light is not visible in occupied space
• Only qualified technicians should install this product*
• Install in accordance with relevant building codes
WARNING
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR DISCONNECT
BEFORE SERVICING
*Installation of this product by anyone other than licensed HVAC or electrical contractors voids warranty.
1. Remove decorative front cover, remove 6 screws holding wire mesh fan guard in place. (Fig. A)
2. Remove 6 screws on each side of the metal plate above the cooling coil.
3. Install lamp with magnetic shield on the backside of metal plate (Fig. B). Lamp should shine down
between coil and blower (Fig. C). Lamp will be in front of coil on PZ and PE models. Lamp cord to be
fed through the existing fan wire chase.
4. Remove control panel screws to access incoming power source. On PH & PE models install power
supply under control panel using double sided tape (Fig. D). On PZ model install power supply inside
the control box.
5. Using the spade and/or the piggyback connectors (Fig. G), connect directly to constant power
source terminals. Use Split-Loom to protect wires.
6. Connect power supply to lamp cord. Connect lamp cord to lamp. Use Zip-Tie and Zip-Tie Base to
bundle and secure excess wire and lamp cord.
7. Apply warning/replacement sticker to inside of the control panel cover.
G
Installation in VRP 07 models
1. Remove top cover to access inside coil area.
2. Lift lid above coil. Position lamp on lid facing down (Fig. E). Cut 2 slits in lid insulation at the magnets
to allow magnets to contact lid.
3. Install ballast in the lower right side of electrical cabinet using the double sided tape.
4. Using the spade or the piggyback connectors, connect directly to constant power source terminals.
5. Remove grommet in the through tting and punch a hole in the center (Fig. F). Push lamp cable
from ballast through the hole and use Split-Loom for protection. Reinstall grommet with cable
atttached and plug into lamp cord. Use Zip-Tie and Zip-Tie Base to bundle and secure any excess
wire or lamp cord.
6. Apply warning sticker to outside of cabinet.
Manufactured and Branded under agreement for Friedrich Air Conditioning, LLC by
Triatomic Environmental Inc.
Fig. A
Fig. B
Fig. C
Fig. D
Fig. E
Fig. F