Installation and Operation Manual PTAC Packaged Terminal Air Conditioners & Heat Pumps SG SERIES 9830 1000_00 (01/15)
Table of Contents Congratulations......................................................................................................................................................................................................................... 3 General Instructions.................................................................................................................................................................................................................. 3 General Specifications....
Congratulations Thank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many years of dependable, efficient operation, maintaining a comfortable temperature and humidity level. Many extra features have been built into your unit to assure quiet operation, the greatest circulation of cool, dry air, and the most economic operation.
General Specifications E MODEL NUMBER PD Engineering Digit Series PD = Friedrich Digital PTAC Design Series Note: All PTAC models with a C design series or later come standard with Diamonblue seacost protection and digital controls. System X = Accessory E = Cooling with or without electric heat H = Heat Pump with Auxiliary Heat Chassis S = Standard Nominal Capacity 07 = 7,000 Btuh 09 = 9,000 Btuh 12 = 12,000 Btuh 15 = 15,000 Btuh Nominal Heater Size (230V or 265V) 2 = 2.
PTAC Installation Recommendations For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances below: Figure 1 PTAC units should be installed no closer than 12" apart when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units. Also, a vertical clearance of 60" should be maintained between units installed.
Wall Sleeve Installation Instructions (PDXWS) NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions completely before attempting installation. WARNING NOTICE DO NOT allow any pitch toward the inside. Falling Object Hazard Flashing on all 4 sides of the opening is recommended.
Alternate Wall Installations Figure 6 Figure 4 Curtain Wall Panel Wall WALL OR WINDOW 1/4" MIN PROJECTION CASE FLANGE (BY OTHERS) OPTIONAL SUBBASE OPTIONAL SUBBASE LEVELING SCREW FRP003 Figure 5 LEVELING SCREW Figure 7 Frame and Brick Veneer Block and Brick Veneer 1/4" MIN PROJECTION 1/4" MIN PROJECTION CONCRETE LINTEL WOOD FRAME STEEL LINTEL STEEL LINTEL 13-3/4" MIN. WITHOUT SUBBASE 11" MIN.
Figure 8 Wall Sleeve Attachment ALTERNATE FASTENING METHODS (Field Supplied) WALL SLEEVE NOTE: The Wall Sleeve must be horizontally level (side-to-side) and pitched 1/4 bubble to the WOOD SCREW outside when installed in an opening. TOGGLE BOLT The mounting hole location EXPANSION should be approximately 2-4” ANCHOR BOLT from the top and bottom of the sleeve. MOUNTING HOLES PLASTIC ANCHORS SCREWS FRP007 Figure 9 Dimensions A ¼" MIN.
5. Drill two 3/16" holes through each side of the sleeve approximately 4" from top and 4" from bottom of sleeve. Screw four #10 x 1" screws (included) or appropriate fasteners for your installation, through the holes in the sides of the wall sleeve. 6. Apply sealant around the wall sleeve where it projects through the inside and outside wall surfaces. Apply the sealant to the screw heads or the tops of the fasteners used in Step #5. Figure 10 7.
PXDR10 Drain Kit Installation Instructions (optional for new construction) NOTE: Determine whether drain will be located within the wall, on the indoor side, or will drain to the exterior of the building. Follow appropriate instructions below depending on your particular type of installation. Internal Drain NOTE: 1. 2. 3. Remove the backing from the gasket and mount it on the flat side of the mounting plate. (See Figure 12, Page 11).
External Drain (for new construction or unit replacement) When using an external drain system, the condensate is removed through either of two drain holes on the back of the wall sleeve. Select the drain hole which best meets your drainage situation and install the drain kit. Seal off the other with a cover plate. Cover Plate Installation 4. Mount the foam gasket to the cover plate. Using two #10 x ½" sheet metal screws (provided), attach the cover plate to the remaining drain hole.
PXGA Standard Grille Installation Instructions WARNING 1. Remove the center support and weatherboard if still installed in the sleeve. 2. Insert six plastic grommets into the grille openings from the outside of the grille as shown in Figure 13. Falling Object Hazard 3. Insert two #8 x ⅜" sheet metal screws (provided) in the top two outside edge plastic grommets, and tighten them half way into the grommets.
A. Electrical Rating Tables All 230/208 volt units are equipped with power cords. NOTE: Use Copper Conductors ONLY. Wire sizes are per NEC, check local codes for overseas applications. Table 1 RECEPTACLES AND FUSE TYPES Voltage 230V 15 Amps Heater Size 2.5 kW 20 265V 30 3.5 kW 5.0 kW 15 20 30 2.5 kW 3.5 kW 5.0 kW FUSE/CIRCUIT BREAKER Use ONLY type and size fuse or HACR circuit breaker indicated on unit’s rating plate. Proper current protection to the unit is the responsibility of the owner.
Table 2 Model PDE/PDH07K PDE/PDH09K PDE/PDH12K PDE/PDH15K PDE/PDH07R PDE/PDH09R PDE/PDH12R PDE/PDH15R Heater kW 2.5 3.5 2.5 3.5 5.0 2.5 3.5 5.0 2.5 3.5 5.0 2.5 3.5 2.5 3.5 5.0 2.5 3.5 5.0 2.5 3.5 5.
Figure 16 Figure 15 TO CHASSIS JUNCTION STRAIGHT CONNECTOR WALL CONNECTION 4.0 IN. JUNCTION BOX GROUND SCREW GROUND WIRE HARNESS EXPOSE WIRES (1.0 IN.) 18.0 IN. TRIM HARNESS TO LENGTH STRIP WIRE ENDS (0.5 IN.) SPACER TO WALL JUNCTION Route the cut ends of harness through the conduit connector assembly and flex conduit sleeve. Be sure to use the supplied conduit bushing to prevent damage to the cord by the conduit.
Chassis Install Preparation Check to be sure the wall sleeve, extension (if used), grille, and drain kit are installed properly before chassis installation. 1. Remove the weatherboard and center support from the sleeve (if still in place). Be sure an outdoor grille is attached. Figure 18 NOTE: To avoid breaking the door or hinge pins, do not apply excessive force when installing.
4. CAUTION Remove shipping screw from the vent door, if present. See Fig 21. Figure 21 Shipping Screw Location Unit Damage Hazard Failure to follow this caution may result in equipment damage or improper operation. Failure to remove shipping tape and screw will prevent fresh air vent door from opening and may result in damage to vent door cable. 3. Carefully remove shipping tape from the front panel and vent door.
Chassis Installation 1. Lift unit level and slide unit into wall sleeve until from seal rests firmly against front of wall sleeve. 3. Place tabs over top rail (1). Push inward at bottom until panel snaps into place (2). 4. Reinstall front panel. See Figure 24. CAUTION Figure 23 Securing Unit Excessive Weight Hazard Use two or more people when installing your air conditioner. Failure to do so can result in back or other injury.
How To Connect IMPORTANT: Please read following electrical safety data carefully. 3. WARNING Electrical Shock and/or Unit Operation and Damage Hazard Failure to follow this warning could result in personal injury or death and/or unit damage. ● Follow the National Electrical Code (NEC) or local codes and ordinances. ● For personal safety, this unit MUST BE properly grounded. ● Protective devices (fuses or circuit breakers) acceptable for unit installations are specified on the nameplate of each unit.
Friedrich PTAC Digital Control and Unit Features The new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air quality and conserve energy. Through the use of specifically designed control software for the PTAC industry Friedrich has accomplished what other Manufacturer’s have only attempted – a quiet, dependable, affordable and easy to use PTAC. Below is a list of standard features on every Friedrich PTAC and their benefit to the owner.
Instant Heat Heat Pump Mode Heat pump models will automatically run the electric heater to quickly bring the room up to temperature when initially energized, then return to heat pump mode. This ensures that the room is brought up to temperature quickly without the usual delay associated with heat pump units. Even Heat Monitoring The digital control monitors indoor conditions to ensure that the room temperature is within five degrees of the setpoint.
System Configuration Fresh Air Vent Control The vent control lever is located on the left side of the unit, behind the front panel. NOTE: Figure 28 Air Vent Control Location VENT CONTROL (Pull lever through label to operate) The vent door shipping hardware must be removed before using the vent control lever. See page 17, Figure 21, (Remove Shipping Screw from Vent Door if present). When vent door is set to CLOSE, only the air inside the room is circulated and filtered, See Figure 28.
Digital Control User Input Configuration The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible and accessible with the front cover removed from the PTAC. Dip Switch Setting 1. Emergency Heat Override – Switch 1 In the unlikely event of a compressor failure a heat pump unit may be switched to operate in only the electric heat mode until repairs can be made. Moving Dip Switch 1 to ‘ON’. 2.
Digital Control Operation Figure 32 Digital Control Panel °F vs. °C Display Heat/Cool Models (PDE) The unit is factory configured to display all temperatures in degrees Fahrenheit (° F). To switch to degrees Celsius press the ‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds. The display will show a ‘C’ as acknowledgement of the change. To revert back to ° F press the ‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds.
Remote Control Thermostat Installation Install Thermostat 1. Approximately 5 ft. from the floor. 2. Close to or in a frequently used room, preferably on an inside wall. 3. On a section of wall without pipes or ductwork. The Thermostat should NOT be mounted: 1. Close to a window, on an outside wall, or next to a door leading outside. 2. Where it can be exposed to direct sunlight or heat, such as the sun, a lamp, fireplace, or any ther temperatureradiating object which may cause a false reading. 3.
Desk Control Terminals The Friedrich PD model PTAC has built-in provisions for connection to an external switch to control power to the unit. The switch can be a central desk control system or even a normally open door switch. For desk control operation connect one side of the switch to the D1 terminal and the other to the D2 terminal (See Figure 31, Page 23). Whenever the switch closes the unit operation will stop. NOTE: The desk control system and switches must be field supplied.
Final Inspection & Start-up Checklist q Inspect and ensure that all components and accessories have been installed properly and that they have not been damaged during the installation process. q Check the condensate water drain(s) to ensure they are adequate for the removal of condensate water, and that they meet the approval of the end user. q Ensure that all installations concerning clearances around the unit have been adhered to.
Basic Troubleshooting COMPLAINT Unit does not operate. COMPLAINT Unit trips circuit breaker or blows fuses. LCDI Power Cord Trips (Reset Button Pops Out) NOTE: A damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and must not be repaired. Unit does not cool/heat room sufficiently, or cycles on and off too frequently 28 CAUSE SOLUTION ●● Unit turned off. ●● Turn unit on ●● Thermostat is satisfied. ●● Raise/Lower temperature setting.
COMPLAINT Unit does not cool/heat room sufficiently, or cycles on and off too frequently CAUSE ●● COMPLAINT ●● Check the heating capacity of your unit. Air conditioners are sized to meet the cooling load and heater size is then selected to meet the heating load. In extreme, northern climates, room air conditioners may not be able to be used as aSOLUTION primary source of heat.
Accessories New Construction Accessories PDXWSA WALL SLEEVE Galvanized zinc coated steel is prepared in an 11-step process, then powder coated with a polyester finish and cured in an oven for exceptional durability. The wall sleeve is insulated for sound absorption and thermal efficiency, 16" High x 42" Wide x 13 3/4" Deep. PDXWSEXT DEEP WALL SLEEVE EXTENSION For use when the wall is thicker than 13 1/4”deep.
New Construction Accessories PDXDAA LATERAL DUCT ADAPTER Attaches to the Friedrich PTAC/PTHP unit to direct up to 35% of the total airflow to a second room. The unit mounted duct plenum features a front mounted aluminum grille that has two positions to provide the most optimal air direction. The air may be directed to either the left or the right of the unit through the supplied 3.5 H" x 7 W" x 47" L plenum. Plenum may be cut to length by the installer.
Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, TX 78216 800.541.6645 www.friedrich.com PD-SERIES PACKAGED TERMINAL AIR CONDITIONERS LIMITED WARRANTY SAVE THIS CERTIFICATE. It gives you specific rights. You may also have other rights which may vary from state to state and province to province. In the event that your unit needs servicing, contact your nearest authorized service center.
Friedrich Air Conditioning Co. 10001 Reunion Place, Suite 500 • San Antonio, Texas 78216 (210) 546-0500 www.friedrich.com Printed in the U.S.A.