SMA Sunny Island Integration Guide

Number each battery 1,2,3,4,5.... until the end of the battery circuit.
Except, if only installing one eVault MAX, number the battery "0".
Protocol ID
1 = Sol-Ark / Any inverter
2 = SMA
3 = Reserved
4 - Victron
5 = Schneider
Inverter Settings
The settings that are to be used to program the SMA inverter are provided in
the table below (Table 1). For detailed information on how to commission the SMA
inverter and navigate through its settings menu, follow the URL
link, https://www.youtube.com/watch?v=n0cYWfk8wXQ, which takes one to the
SMA's tutorial video for SMA 6048-US.
Note: Please make sure to update Sunny Island Firmware to version 7.3.04 or
better
SMA Settings for Closed Loop Operation
All unspecified settings will remain at factory values
Password for SMAe inverter is the Sum of AH in the Password Menu
Ex. 105 Ah Total = 1 + 0 + 5 = 6
Number
Name Description eFlex
eVault
MAX
210-02
InvChrgCurMax
Max AC Charge Current
100A each
180A each
221-01
BatTyp
Battery Type
221-02 BatCpyNom Nominal Battery Capacity
105 Ah
each
360 Ah
each
222-01
BatrChargCur
Charging Current
80A each
160A each
222-02
AptTmBoost
Absorb time for nominal charge
222-03
AptTmFul
Absorb time for full charge
222-04
AptTmEq
Absorb time for equalize charge
1 hr
222-05
CycTmFul
Full charge timer