Installation Instructions for Remote Condensing Unit

9
REMOTE CONDENSING UNIT
Refrigeration line installation
3
3.2
2. Leak check eld joints.
3. Evacuate line set via the condensing unit service valves.
5. Open the liquid line service valve and suction line service valve on the condensing unit.
6. Connect the self-sealing liquid and suction line quick disconnects to the evaporator.
7. Open the liquid line valve on the receiver, then the suction line valve on the compressor unit.
8. Liquid charge unit through liquid line shut off valve on the evaporator unit or receiver valve on
the condensing unit.
R404A ice machine charge specications for 1810/2110 models with line runs up to 75 ft. (up to 22.8 m):
Ice machine evaporator holding charge 0.5 lbs (0.23 kg)
Condensing unit holding charge 0.5 lbs (0.23 kg)
Charge at installation 14 lbs (6.35 kg)
Total charge: 14.5 lbs (6.57 kg)
9. Isolate the refrigerant tank from high pressure side on the system.
10. Turn on power to condensing unit and evaporator unit.
11. Complete system charge through low pressure side.