Operation and Service Manual

HC_1810R/N, HC_2110R/N, HM_1810R/N, HM_2110R/N 5
Specifications
Electrical
Separate, dedicated circuit and equipment ground required.
Evaporator unit
Standard electrical: 115/60/1
Maximum fuse: 15A
Amperage: 5A
Condensing unit
1810 Single-Phase 1810 3-Phase 2110 Single-Phase 2110 3-Phase
Electrical 208-230V, 60Hz
Max Circuit HVACR breaker size 45A 25A 45A 30A
Min Circuit Ampacity 26.2A 15.7A 27.1A 19.9A
Evaporator plumbing
§ 3/8" OD push-in water inlet (connection inside machine) - 3/8" OD tubing required.
§ Water shut-off recommended within 10 feet (3 m).
§ Follett recommends installation of Follett water filter system (part# 00130286) in ice machine inlet water
line.
Flush drain plumbing
§ 3/4" MPT flush drain connection at the rear of the machine.
§ Drain must slope 1/4" inch per foot (6 mm per 30.4 cm).
§ Drain line should not be shared with any other piece of equipment.
§ Drain line cannot be reduced to a size smaller than 1 inch.
§ Drain should be piped without a vent.
3/4" barb x 3/4" FPT
1" Stand pipe/Drain
2 ft. x 1" OD
silicone tubing
Minimum 8"
radius
3/4" MPT x 1" slip
1" PVC Drain
2 ft. x 1" OD
silicone tubing
3/4" MPT x 1" slip
3/4" barb x 3/4" FPT
1'
1/4" per foot
(6,4 mm per 0,3 m)