Pre Pleat 40 Data Sheet

CFM PD CFM PD CFM PD CFM PD
10x20x2 417 0.11 694 0.21 4.3 0.4 417 0.10 694 0.20 6.2 0.5
12x20x2 500 0.11 833 0.21 4.8 0.5 500 0.10 833 0.20 7.2 0.5
12x24x2 600 0.11 1000 0.21 5.8 0.6 600 0.10 1000 0.20 8.7 0.6
14x20x2 583 0.11 972 0.21 5.8 0.5 583 0.10 972 0.20 8.6 0.6
14x25x2 729 0.11 1215 0.21 7.2 0.7 729 0.10 1215 0.20 10.8 0.8
15x20x2 625 0.11 1042 0.21 6.2 0.6 625 0.10 1042 0.20 9.1 0.7
16x20x2 667 0.11 1111 0.21 6.7 0.6 667 0.10 1111 0.20 9.6 0.7
16x25x2 833 0.11 1389 0.21 8.4 0.7 833 0.10 1389 0.20 12.0 0.9
18x24x2 900 0.11 1500 0.21 8.7 0.8 900 0.10 1500 0.20 13.3 0.9
18x25x2 938 0.11 1563 0.21 9.0 0.8 938 0.10 1563 0.20 13.8 1.0
20x20x2 833 0.11 1389 0.21 8.2 0.7 833 0.10 1389 0.20 12.0 0.9
20x24x2 1000 0.11 1667 0.21 9.8 0.9 1000 0.10 1667 0.20 14.4 1.0
20x25x2 1042 0.11 1736 0.21 10.2 0.9 1042 0.10 1736 0.20 15.0 1.1
24x24x2 1200 0.11 2000 0.21 11.5 1.0 1200 0.10 2000 0.20 17.3 1.2
25x25x2 1302 0.11 2170 0.21 12.6 1.1 1302 0.10 2170 0.20 19.3 1.3
A B D
10x20x2 9 1/2" 19 1/2" 1 3/4"
12x20x2 11 1/2" 19 1/2" 1 3/4"
12x24x2 11 3/8" 23 3/8" 1 3/4"
14x20x2 13 1/2" 19 1/2" 1 3/4"
14x25x2 13 1/2" 24 1/2" 1 3/4"
15x20x2 14 1/2" 19 1/2" 1 3/4"
16x20x2 15 1/2" 19 1/2" 1 3/4"
16x25x2 15 1/2" 24 1/2" 1 3/4"
18x24x2 17 3/8" 23 3/8" 1 3/4"
18x25x2 17 1/2" 24 1/2" 1 3/4"
20x20x2 19 1/2" 19 1/2" 1 3/4"
20x24x2
19 3/8"
23 3/8"
1 3/4"
Media Area
(Sq. Ft.)
Weight
Each (lbs)
2''
Standard
Capacity
10 ppf
High
Capacity
15 ppf
Nominal
Size (in.)
Actual Size
Nominal
Depth
(in.)
Nominal
Size AxBxD
(in.)
Standard Capacity
High Capacity
300 FPM 500 FPM
Media Area
(Sq. Ft.)
Weight
Each (lbs)
300 FPM 500 FPM
20x24x2
19 3/8"
23 3/8"
1 3/4"
20x25x2 19 1/2" 24 1/2" 1 3/4"
24x24x2 23 3/8" 23 3/8" 1 3/4"
25x25x2 24 1/2" 24 1/2" 1 3/4"
Notes:
1. PD represents pressure drop in inches w.g. The
is 1.0 in. w.g. System design may dictate a lower
change-out point.
2. Efficiency is not affected by the conditioning steps outlined in
ASHRAE 52.2-2007 per Appendix J.
Qty:
Qty:
Qty:
Specifications:
1. Media is made of 100% synthetic non-woven proprietary media that can
be recycled.
2. The media is supported by an expanded metal continuously laminated on
the air leaving side to provide pleat stability while eliminating flutter.
3. Pleat design is a V-Pleat that aids in pressure drop while reducing energy
cost and allowing total media usage and provides maximum airflow and dust
holding capacity.
4. Frame is a two-piece construction, made of a heavy duty 24 point moisture resistant
material. Diagonal and horizontal support members are bonded to the media on both sides.
5. Highest dust holding capacity and lowest pressure drop in the industry
6. Maintains a mechanical MERV 8 per ASHRAE Standard 52.2. Classified UL
900 Class 2.
Customer order No.
Flanders order No.
Title:
2 Inch Deep Pre Pleat 40 LPD UL
900
Model No.
Model No.
Customer
Standard Capacity 80055.02xxxx
High Capacity 80255.02xxxx
Model No.
900 Class 2.
7. Maximum Operating Temperature is 180
°F.
Rev.
B
Drawing No. Date
2" Pre-Pleat 40 LPD 12/23/2011
900