Installation Guide

15
ELECTRICAL CONNECTION
Power supply cord with
NEMA 14-50P plug
Standard NEMA 14-50R wall receptacle
IMPORTANT!
This cooker must be connected to the electricity supply only by an authorised person.
Your cooker is supplied with a certified 4 prong NEMA 14-50P power cord for your protection against shock hazard and should be plugged
directly into a properly grounded socket.
Do not under any circumstances cut or remove the forth (ground) prong from the power plug.
Do not ground to a gas pipe.
Do not have a fuse in the neutral or ground circuit.
Do not use an extension cord.
Check with a qualified electrical installer if you are not sure if the range is properly grounded.
If codes permit, and a separate ground wire is used, it is recommended that a qualified electrical technician determines the ground path
and wire gauge are in accordance with local codes.
Be sure that the electrical connection and wire size are adequate and in conformance with:
ANSI/NFPA 70 latest addition and local codes and ordinances.
CSA standard C22.1, Canadian Electrical Code, Part 1 – latest edition and local codes and ordinances.
When a 4-wire, two phase 120/240V or 120/208V 60Hz AC only electrical supply is available a 50 amp maximum circuit protection is
required, fused on both sides of the line.
Replacing the power cord.
Replacements should only be made by qualified electrical technicians.
If replacing the power cord, use only a suitable UL or CSA approved one.
Tighten the power cord using the power cord strain relief bracket supplied with the appliance.
Allow enough slack to easily attach the cord terminals to the terminal block.
Power supply cord with
NEMA 14-50P plug
Standard NEMA 14-50R
wall receptacle
WARNING!
Electrical Shock Hazard
Electricity ground range.
Failure to follow these
instructions can result in death,
fire, or electrical shock.
WARNING!
VERY IMPORTANT
To avoid electrical shock
hazard, before installing the
appliance, switch power OFF
at the service panel and lock
the panel to prevent the
power from being switched
on accidentally.
Location of
nameplate
RANGE RATING *
SPECIFIED RATING OF POWER SUPPLIED
CORD KIT AND CIRCUIT PROTECTION
Induction models
AC 120/208 V 60 Hz 11110 W MAX NEC CALCULATED LOAD 40 A*
AC 120/240 V 60 Hz 12340 W MAX NEC CALCULATED LOAD 40 A*
INDUCTION POWER = 7400 W MAX
Ceramic models
AC 120/208 V 60 Hz 8668 W MAX 50 A
AC 120/240 V 60 Hz 11540 W MAX 50 A
* The NEC calculated load is less than the total connected load listed on the rating label.