62 Series - Power relays 16 A
Technical data
Insulation according to EN 61810-1
2 CO - 3 CO 2 NO - 3 NO
Nominal voltage of supply system V AC 230/400 230/400
Rated insulation voltage V AC 400 400
Pollution degree 3 3
Insulation between coil and contact set
Type of insulation Reinforced Reinforced
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 6 6
Dielectric strength V AC 4,000 4,000
Insulation between adjacent contacts
Type of insulation Basic Basic
Overvoltage category III III
Rated impulse voltage kV (1.2/50 µs) 4 4
Dielectric strength V AC 2,500 2,500
Insulation between open contacts
Type of disconnection Micro-disconnection Full-disconnection
Overvoltage category III
Rated impulse voltage kV (1.2/50 µs) 4
Dielectric strength V AC/kV (1.2/50 µs) 1,500/2 2,500/4
Conducted disturbance immunity
Burst (5...50)ns, 5 kHz, on A1 - A2 EN 61000-4-4 level 4 (4 kV)
Surge (1.2/50 µs) on A1 - A2 (differential mode) EN 61000-4-5 level 4 (4 kV)
Other data
Bounce time: NO/NC ms 1/5 (changeover) 3/— (normally open)
Vibration resistance (10…150)Hz: NO/NC g 20/8
Shock resistance g 15
Power lost to the environment 2 pole (CO) 3 pole (CO) 2 pole (NO) 3 pole (NO)
without contact current W 1.3 1.3 3 3
with rated current W 3.3 4.3 5 6
Recommended distance between relays mounted on PCB mm 5