Datasheet

22 Series - Modular contactors 25 A
Contact specification
H 22 - Maximum DC1 breaking capacity
R 22 - Coil operating range v ambient temperature
Coil specifications
Nominal Coil Operating range Rated coil
voltage code
consumption
U
N
U
min
U
max
I
N
at U
N
(AC)
VVVmA
12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42
60 0.060 48 66 33
120 0.120 88 138 16.5
(110...125)
230
184 (AC) 264 (AC)
(230...240 AC)
0.230
176 (DC) 242 (DC)
8.7
(220 DC)
AC/DC version data (type 22.34)
Nominal Coil Operating range Rated coil
voltage code
consumption
U
N
U
min
U
max
I
N
at U
N
(AC)
VVVmA
12 0.012 9.6 13.2 165
24 0.024 19.2 26.4 83
48 0.048 38.4 52.8 42
60 0.060 48 66 33
120 0.120 88 138 16.5
(110...125)
230
184 (AC) 264 (AC)
(230...240 AC)
0.230
176 (DC) 242 (DC)
8.7
(220 DC)
AC/DC version data (type 22.32)
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of 100·10
3
can be expected.
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
DC breaking current (A)
DC voltage (V)
Ratings and utilization categories according to EN 61095 : 2009
Utilization Typical Load Rated Rated Rated electrical life (cycles)
category applications characteristics current operational 2-pole 2-pole 4-pole 4-pole
( A ) voltage AgNi contacts
AgSnO
2
contacts
AgNi contacts
AgSnO
2
contacts
( V )
(22.32...1xx0) (22.32...4xx0) (22.34...1xx0) (22.34...4xx0)
across
between
the pole
phases
AC-7a
Slightly
cos ϕ = 0.8 25 250 440
70 · 10
3
(NO)
30 · 10
3
150 · 10
3
(NO)
30 · 10
3
inductive loads 30 · 10
3
(NC) 100 · 10
3
(NC)
AC-7b Motor loads
cos ϕ = 0.45
10 250 440 30 · 10
3
30 · 10
3
30 · 10
3
30 · 10
3
I
making
= 6 I
breaking
Compensated
cos ϕ = 0.9
AC-7c electric discharge
C = 10 μF/A
10 230 400 30 · 10
3
30 · 10
3
lamps
5