User's Manual

USER MANUAL
TCM 300 / TCM 300C / TCM 300U
TCM 320 / TCM 320C / TCM 320U
3.5 Operating modes
Mode
Function
Output signal description
No. of
channels
0
Unidirectional serial
interface compatible
with TCM 220C, no
teach-in capability
SER_TX: UART output, supplies standard
data blocks of information from all received
EnOcean radio telegrams (9600 bps; 8 data
bits, no parity bit, one start bit, one stop bit).
For further information see chapter A.1
1
Bidirectional serial
interface, teach-in
capability for up to
30 entries
1
SER_RX, SER_TX: Asynchronous bidirectional
Interface, supplies standard data blocks of
information from all received EnOcean radio
telegrams (9600 bps; 8 data bits, no parity
bit, one start bit, one stop bit). For further
information see chapter A.1
LRN_TOGGLE: Learning mode status indica-
tor
2
Rocker Switch - 1
channel, teach-in ca-
pability for up to 30
entries
1
Supplies the desired logic switching state
“on/off” at CHANNEL0 when pushing the
switch rockers
1
3
Rocker Switch - 4
channels, teach-in
capability for up to
30 entries
2
Same as Mode 2 but operation of 4 receiver
channels (CHANNEL0, CHANNEL1, CHAN-
NEL2, CHANNEL3)
4
4
Dimming - 1 channel,
teach-in capability
for up to 30 entries
1
PWM is the PWM output
I-button pressed for shorter than 0.5 s: ON
(Restore duty cycle stored before last
switch-off).
O-button pressed for shorter than 0.5 s:
OFF
O-/I-button pressed longer than 0.5 s:
Duty cycle variation from 10% up to 100%
(O=less, I=more; ~300 PWM steps, in-
crement every 15 ms). Duty cycle variation
stops when button is released.
PWM_IND is active as long as duty cycle is
not 0%
1
5
Reserved
1
Each rocker of a PTM transmitter is counted as 1 entry
2
Each rocker is counted as 1 entry. If the same rocker is teached into several channels, 1
entry per channel is needed.