Data Sheet

HUMIDITY TEMPERATURE CONTROLLER
EHTC7425A
%RH
°C
HEAT
%RH
Fan
SET
Rotate
L
R
C(on/off)
HSET
TSET
ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER
Thank you for choosing Humidity and Temperature ControllerENDA EHTC7425A
OUTPUT
Sensor Supply
15VDC , Max. 50mA
30.000.000 Switching for no-load operation; 300.000 switching for 10A resistive load at 250VAC.
HOUSING
Housing type
Suitable for flush-panel mounting according to DIN 43 700.
Dimensions
W72xH72xD97mm
Weight
Approx. 350g (after packing)
Enclosure Material
Self extinguishing plastics
±%0,5 (Full scale)
Approx. 100kΩ
Approx. 10Ω
INPUTS
Input Resistance
Measurement Range
Measurement Accuracy
Input Type
0-20mA
4-20mA
1-5V
0-10V
AS
DS
-40.0....125.0 C
0....100 %RH
º
---------------
EHTD-CB-10 0
TECHNICAL SPECIFICAT IONS
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept anycompensations fo r personal injury, material damage orcapital disadvantages.
ENVIRONMENTAL CONDITIONS
Height
Max. 2000m
80 up to 31Relative humidity for temperatures% °C decreasing linearly 50% at 40°C., to
Ambient/stroge temperature
Max. Relative humidity
0 ... +50°C/-25 ... 70°C (Without icing)
Rated pollution degree
According to EN 60529 Front panel : IP6 , Rear5 panel : IP20
Life expectancy for relay
7 x mm sized.
4 digits display.
0/4-20mA, 0-10V, 1- 5V analog or digital input (Specify at Order).
Heating or cooling control selection.
PID, On-Off Temperature control selection.
PID Auto-calculation (SELF TUNE).
Humidification or drying control selection.
Internal supply output for sensor.
Time and temperature-dependent fan relay output selection.
2 Relay outputs with time setting for incubation operations.
Adjustable buzzer alarm feature f or measurement values.
CE marked according to European Norms.
2 72
Dual
230V AC 110V AC ±10%, 50/60Hz or 10...30V DC / 8...24V AC
Supply
Power consumption
Max. 7VA
2.5mm² screw-terminal connections
Wiring
EMC
Safety requirements
EN 61326-1: 2013
EN 61010-1: 2010 (pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
0~20mA / 0~10V can be selected for analog output sensors. Temperature range for digital output Enda Sensor is -40~125°C
Temperature input range
Humidity input range
0~20mA / 0~10V can be selected for analog output sensors. Humidity range for digital output Enda Sensor is 0~100 RH
When thede vice is in current measurement mode, the input impedance is 10 . Therefore voltage input should not be connected to the device while
in current mode. Otherwise the device will deteriorate. If it is necessary to switch from the voltage measurement mode to the current measurement
mode while the device is running, It must be removed and the n changed to one of the input type current measurement modes.
Ω
Max. 12VDC 30mA.
SSR Output
KEEP AWAY device from exposed to corrosive, volatile and flammable gases or liquids and DO NOT USE the device in similar hazardou s
locations.
Avoid any liquid contact when the device is switched on.
DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.
Please see page 6 for
Modbus Connection
Diagram.
Order Code : EHTC7425A - - - -
1
2 3 4
1 - Input
AS.......Analog Input
DS......Digital Input
2 - Supply Voltage
230..........230V AC
110..........110V AC
SM........10...30V DC
8...24V AC
3 ModBus
Specify at Order .
-
( )
Blank......N/A
RS ...... ModBusI ...
4 SSR
Applies to the heat output .
-
( )
Blank......N/A
SSR ......... ModBus
Sensor must be
ordered separately.
english
EHTC7425A-E-12102021
1 / 7.
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)74 51 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9

Summary of content (8 pages)