Instructions

8. Specifications
Device Type : Temperature Controller
Housing&Mounting : 48 mm x 48 mm x 95 mm 1/16 DIN 43700 plastic housing
for panel mounting. Panel cut-out is 46 x 46 mm
Protection Class : NEMA 4X (IP65 at front, IP20 at rear)
Weight : Approximately 0.16 Kg.
Environmental Ratings : Standard, indoor at an altitude of less then 2000 meters
with non-condensing humidity
o o o o
Storage/Operating Temperature : -40 C to +85 C / 0 C to +50 C
Storage/Operating Humidity : 90 % max. (Non-condensing)
Installation : Fixed installation
Over Voltage Category : II
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power : 230 V V (±15%) 50/60 Hz. 3 VA
115 V V (±15%) 50/60 Hz. 3 VA
24 V V (±15%) 50/60 Hz. 3 VA
Temperature Inputs : NTC, PTC, TC, RTD
NTC Input Types : N
Thermocouple Input Types : J,
Thermoresistance Input Type :
Accuracy : ± 1% of FS for Thermocouple, Thermoresistance
Cold Junction Compensation : Automatically ± 0.1°C/1°C
Line Compensation : Maximum 10 W
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Forms : ON / OFF
Relay Outputs : 7 A@250 V V at resistive load
(Electrical Life : 100.000 Operation (Full Load))
Output
Display : 10 mm Red 3 digits LED display
Led Indicators : SET (Green), OUT (Red), PROG (Red) 3 mm
Approvals : UL Recognized Component (File No : E 254103),
,
Type-1 Enclosure Mounting
24 V (-%15, +%10) 50/60 Hz. 3 VA
TC (10 kW @.25 °C )
PTC Input Type : PTC (1000 W @.25 °C )
Opsiyonel SSR Driver : Maximum 23 mA, Maximum 15 V Z
W
K (IEC584.1)(ITS90)
PT 100 (IEC751(ITS90)
CECE
31