Accessing an RPC2 Communications Module via the Web Interface
Emerson
®
RPC2
™
16
4.2 Summary Tab
Click the Summary tab (Figure 11) to view recent events as well as rack PDU status information.
This tab gives access to a rack PDU’s ID, status, number of receptacles and how many are turned On
as well as measurements and utilization information. Click on a rack PDU under the PDU Status
heading to open it in the PDU Explorer tab (refer to 4.3 - PDU Explorer Tab for more information).
Events information include:
• Date/Time: Date and time of occurrence
• Code—Identifier for troubleshooting
• 100-113—System level events
• 200-207—PDU level events
• 300-305—Branch level events
• 400-407—Receptacle level events
• 500-512—Sensor level events
• Level—Where event occurred: Receptacle, Branch, System
• ID—Identifying information of where event occurred
• Event—Severity of Event: Notification, Warning or Alarm
• State—Whether event notification has been sent (notified); for alarms, either active or cleared
• Description—Information about the event
Figure 11 Summary tab
System
Information
(IP address,
firmware
version, contact
information for
events and
alarms)
Overall
Status
Events Table
Click here to
view a rack
PDU’s status
in the PDU
Explorer tab
Status of this rack PDU
State shows
status of event
Event Code