User manual

Accessing an RPC2 Communications Module via the Web Interface
Emerson
®
RPC2
16
4.2 Summary Tab
Click the Summary tab (Figure 11) to view recent events as well as rack PDU status information.
This tab gives access to a rack PDU’s ID, status, number of receptacles and how many are turned On
as well as measurements and utilization information. Click on a rack PDU under the PDU Status
heading to open it in the PDU Explorer tab (refer to 4.3 - PDU Explorer Tab for more information).
Events information include:
Date/Time: Date and time of occurrence
Code—Identifier for troubleshooting
100-113—System level events
200-207—PDU level events
300-305—Branch level events
400-407—Receptacle level events
500-512—Sensor level events
Level—Where event occurred: Receptacle, Branch, System
ID—Identifying information of where event occurred
Event—Severity of Event: Notification, Warning or Alarm
State—Whether event notification has been sent (notified); for alarms, either active or cleared
Description—Information about the event
Figure 11 Summary tab
System
Information
(IP address,
firmware
version, contact
information for
events and
alarms)
Overall
Status
Events Table
Click here to
view a rack
PDU’s status
in the PDU
Explorer tab
Status of this rack PDU
State shows
status of event
Event Code