Specification Sheet

ERFPM28K MOUNTING FRAME INSTRUCTIONS
1.Cut a square rectangular wall opening
37-1/2"
(953mm) W x 37-3/4" (959mm) H and 4-1/2"
(114mm) above the floor line. These dimensions
are required to obtain proper rim and bubbler
heights for compliance with ANSI standard
A117.1. (See Figure 2)
2.Reinforce the wall opening on all sides so that it
will adequately support the water fountain. This
reinforcement must support up to 150 lbs static
load and provide a means for securing the frame
assembly in place.
NOTE: Building construction must allow for
adequate air flow on both sides and top of remote
chiller unit. Minimum of 4" (102mm) is required.
(See Figures 1 & 2)
3.Install plumbing and electrical rough-ins. See
Figure 1 for location of the supply water inlet to
chiller and for the location of the waste water
outlet. A junction box for a (3) wire, 10 amp branch
circuit is provided on the inside of the chiller.
(Standard 120 Volts, 60 Hz and single phase)
See Figure 2 for the electrical inlet location.
4.Remove frame assembly and related hardware
from packaging. Attach the two frames together
thru the upright supports with (4) 5/16" x 3/4"
(19mm) long bolts and nuts (provided). Tighten
securely.
NOTE: Frame with higher upper channel to be on
left side.
5.Install the frame assembly squarely in wall
opening with frame upright support edges flush
with the finished wall face. Secure the frame to the
wall thru holes with (12) 5/16" x 2" (51mm) long
lag bolts or screws (not provided). Tighten securely.
NOTE: Be sure that frame is squared in location.
Do not use less than required screw quantity and
size.
6.Attach the chiller shelf support rods to the right
side frame uprights at the second set of holes
counting from the bottom and to the shelf at the
(2) side holes. Line up the other shelf holes with
the frame bottom holes and fasten the assembly
to the wall using appropriately sized wood screws
or bolts and nuts (not provided). (See Figure 2)
FIG.1
FIG. 2
IMPORTANT!
INSTALLER PLEASE NOTE:
The grounding of electrical equipment such as tele-
phone, computers, etc., to water lines is a common
procedure. This grounding may be in the building or
may occur away from the building. This grounding
can cause electrical feedback into a water cooler,
creating an electrolysis which causes a metallic
taste or an increase in the metal content of the
water. This condition is avoidable by using the proper
materials as indicated below.
The drain fittings which are provided by the installer
should also be plastic to electrically isolate the cooler
from the building plumbing system.
FINISHED FLOOR
*A.D.A. REQUIREMENT
NOTE: SERVICE STOP NOT INCLUDED.
20-3/8"
(517mm)
6-1/2"
(165mm)
39-1/2"
(1003mm)
20-7/16"
(519mm)
27"*
(686mm)
ELECTRICAL INLET
1-1/8"
(29mm)
11"
(279mm)
4-1/2"
(114mm)
3-1/2"
(89mm)
31-1/4"
(794mm)
37-1/4"
(946mm)
1-1/4" (32mm)
TRAPS FURNISHED
BACK WALL LINE
12"
(305mm)
MINIMUM DEPTH
18-3/4"
(476mm)
1/4" O.D. TUBE CONNECT
(CHILLER WATER OUTLET)
8-1/8"
(206mm)
9-3/8"
(238mm)
FILTER
LOCATION
(OPTIONAL)
3-13/16"
(97mm)
12-1/8"
(308mm)
38-1/2"
(978mm)
6-5/8"
(168mm)
12-1/8"
(308mm)
3-13/16"
(97mm)
WALL LINE
12-1/4"
(311mm)
18"
(457mm)
4"
(102mm)
3/8" O.D. COPPER TUBE
WATER INLET ON CHILLER
SHUT OFF VALVE BY OTHERS
3-1/8"
(80mm)
1-1/8"
(29mm)
7-1/16"
(179mm)
1-5/8"
(41mm)
NOTE: WATERFLOW
DIRECTION
SERVICE STOP
(NOT FURNISHED)
3/8" O.D. TUBE CONNECT
COLD WATER SUPPLY
BY OTHERS
1/4" O.D. TUBE
WATER INLET
TO COOLER
BUILDING WATER
INLET
OPERATION OF QUICK CONNECT FITTINGS
SIMPLY PUSH IN
TUBE TO ATTACH
TUBE IS SECURED
IN POSITION
PUSH IN COLLET
TO RELEASE TUBE
PUSHING TUBE IN BEFORE
PULLING IT OUT HELPS TO
RELEASE TUBE
AB
C
Elkay
2222 Camden Court
Oak Brook, IL 60523
elkayusa.com
Printed in U.S.A.
©2006 Elkay
12-15G (Rev. 7/06)
No Lead Two-Level Soft Sides
®
Water Cooler
Wall Mount Barrier-Free Access
Model ERFPM28K
®
ROUGH-IN DIMENSIONS
HOOK RODS (2)
P/N 101567443730
INSTALL (3) SCREWS
(P/N 111008343890)
IN FRAME BEFORE
INSTALLING IN OPENING
ELECTRICAL INLET
LOCATION ON
CHILLER
WOOD OR STEEL FRAME
SHOWN (NOT PROVIDED)
FLOOR LINE
BACK OF
WALL TO BE
12" (305mm)
MIN. DEPTH
TO FLOOR LINE
1-1/8"
(29mm)
8"
(203mm)
5-1/8"
(130mm)
37-1/2"
(953mm)
4-1/2"
(14mm)
37-3/4"
(959mm)
BOLT FRAMES TOGETHER
WITH 5/16" X 3/4" (19mm) BOLTS
(4 REQ'D- PROVIDED)
P/N 111577243890
SCREWS OR BOLTS
(NOT PROVIDED)
5/16" HEX NUT
(4 REQ'D - PROVIDED)
P/N 111577343890
FRAME
5/16" SCREWS OR BOLTS
(12 REQ'D- NOT FURNISHED)