Manual

Operating instructions
K3G280-AU11-C6
Translation of the original operating instructions
3.2 Nominal data
Motor M3G084-GF
Phase 3~
Nominal voltage / VAC 400
Nominal voltage
range / VAC
380 .. 480
Frequency / Hz 50/60
Type of data definition ml
Speed / min
-1
3100
Power input / W 1000
Current draw / A 1.6
Min. ambient temperature
/ °C
-25
Max. ambient
temperature
/ °C
60
ml = Max. load · me = Max. efficiency · fa = Running at free air
cs = Customer specs · cu = Customer unit
Subject to alterations
3.3 Data according to ErP directive
Installation category A
Efficiency category Static
Variable speed drive Yes
Specific ratio
*
1.01
*
Specific ratio = 1 + pfs / 100 000 Pa
Actual Request
2013
Request
2015
Overall efficiency ηes / % 61.4 47.5 51.5
Efficiency grade N 71.9 58 62
Power input Ped / kW 0.99
Air flow qv / m³/h 2675
Pressure increase total psf / Pa 758
Speed n / min
-1
3115
Data definition with optimum efficiency.
The ErP data is determined using a motor-impeller combination in a standardised
measurement configuration.
3.4 Technical features
Mass 11.8 kg
Size 280 mm
Surface of rotor Coated in black
Material of electronics
housing
Die-cast aluminium, coated in black
Material of impeller Aluminium sheet, white plastic-coated
Material of mounting
plate
Sheet steel, galvanised and coated in
white
Material of support
bracket
Steel, galvanised and coated in black
Material of inlet nozzle Sheet steel, galvanised and coated in
white
Number of blades 7
Direction of rotation Clockwise, seen on rotor
Type of protection IP 54
Insulation class "B"
Humidity class F5
Mounting position Shaft horizontal or rotor on bottom; rotor
on top on request
Condensate discharge
holes
Rotor-side
Operation mode S1
Motor bearing Ball bearing
Technical features - Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (programming)
- Alarm relay
- Output limit
- Motor current limit
- RS485 MODBUS RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
<= 3.5 mA
Electrical leads Via terminal box
Motor protection Thermal overload protector (TOP) wired
internally
Protection class I (if protective earth is connected by
customer at the connection point of the
housing)
Product conforming
to standard
EN 61800-5-1; CE
Approval EAC
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.5 Mounting data
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.6 Transport and storage conditions
; Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+80 °C
Min. permissible
ambient motor temp.
(transp./storage)
-40 °C
Item no. 51319-5-9970 · ENG · Revision 82513 · Release 2014-08-05 · Page 5 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com