Owner manual

Operating instructions
G3G250-GN17-01
Translation of the original operating instructions
6. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES
Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.
WARNING
Terminals and connections have voltage even with a
unit that is shut off
Electric shock
Wait five minutes after disconnecting the voltage at all poles
before opening the device.
CAUTION
If the control signal of a blower that is connected to the
power system is removed, the motor can restart
automatically.
Danger of injury
When working on the blower, switch off the mains supply
voltage and secure it from being switched on again.
Wait until the device stops.
CAUTION
Electrical load after device is switched off
Electric shock in case of contact
Wait for five minutes after disconnecting the voltage at all
poles before touching the unit.
CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.
Danger of injury
Keep out of the danger zone of the device.
When working on the device, switch off the mains
supply voltage and secure the latter from being switched on
again.
Wait until the device stops.
After working on the device, remove any used tools or
other objects from the device.
If the blower remains out of use for some time, e.g. when in
storage, we recommend switching the blower on for at least 2
hours to allow any condensate to evaporate and to move the
bearings.
Malfunction/error Possible cause Possible remedy
Impeller running
roughly
Imbalance in rotating
parts
Clean the device; if
imbalance is still
evident after
cleaning, replace the
device.
If you have
attached any weight
clips during cleaning,
make sure to
remove them
afterwards.
Motor does not turn Mechanical blockage Switch off, de-
energise, and
remove mechanical
blockage.
Mains supply
voltage faulty
Check mains supply
voltage,
restore power
supply,
apply control signal.
Faulty connection De-energise, correct
connection, see
connection diagram.
Overtemperature of
electronics/motor
Insufficient cooling Improve cooling. Let
the device cool
down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Ambient temperature
too high
Reduce the ambient
temperature.
Reset by reducing
control input to 0.
Unacceptable
operating point
Correct the operating
point. Let the device
cool down.
Deflagration Leakage of the
handled air/gas
mixture
Check for leaks;
replace blower if not
properly sealed
If you have any other problems, contact ebm-papst.
6.1 Cleaning
NOTE
The device does not need to be cleaned.
6.2 Safety test
NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
What has to
be tested?
How to test? Frequency Which
measure?
Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact
Visual inspection At least every
6 months
Repair or
replacement of
the device
Item no. 50133-5-9970 · Revision 67913 · Release 2009-10-14 · Page 11 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com