Datasheet

03/21/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 5
Overload�relay�4�-�6A
Part�no. ZB12-6
Article�no. 278439
Program
Product range Overload relay ZB up to 150 A
Phase-failure sensitivity IEC/EN 60947, VDE 0660 Part 102
Description Test/off button
Reset pushbutton manual/auto
Trip-free release
Mounting type Direct mounting
I
r
A 4 - 6
Contact sequence
Auxiliary contacts
N/O = Normally open 1 N/O
N/C = Normally closed 1 N/C
For use with DILM7, DILM9, DILM12, DILM15,
DIULM7, DIULM9, DIULM12,
SDAINLM12,
SDAINLM16,
SDAINLM22
DS7-34…SX005…
Short-circuit protection
Type “1” coordination gG/gL A 25
Type “2” coordination gG/gL A 20
Notes
Overload release: tripping class 10 A
Short-circuit protection: Observe the maximum permissible fuse of the contactor with direct device mounting.
Suitable for protection of Ex e-motors.
II (2) GD
PTB 10 ATEX 3010
Observe manual AWB2300-1527D/GB.
Notes
Fitted directly to the contactor
1 Contactor
Approbationen
UL approval Yes
CSA approval Yes