Datasheet

03/26/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 6
Enclosed °C - 25 - 40
Mounting position As required
Mechanical shock resistance to IEC 60068-2-27 Half-
sinusoidal
shock
20 ms
g > 15
Contacts
Rated operational voltage U
e
V
AC
690
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated uninterrupted current I
u
A
open I
u
A 20
Enclosed I
u
A 20
Load rating with intermittent operation, class 12
AB 25 % DF x I
e
2
AB 40 % DF x I
e
1.6
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A
gG/
gL
20
Rated short-time withstand current (1 s current) I
cw
A
rms
320
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between the contacts V
AC
440
Switching angles ° 90
60
45
30
Contact units 11
Double-break contacts max. 22
Current heat loss per contact at I
e
W 0.6
Terminal�capacities
Solid or stranded
mm
2
1 x (1 - 2.5)
2 x (1 - 2.5)
Flexible with ferrule to DIN 46228
mm
2
1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Terminal screw M3.5
Tightening torque Nm 1
Switching�capacity
AC x U
s
Rated making capacity cos ϕ = 0.35 A 130
Rated breaking capacity, motor load switch cos ϕ = 0.35 A
230 V A 100
400 V A 110
500 V A 80
690 V A 60
Rated operational current 440 V load-break switch AC-21A I
e
A 20
Rating, AC-3 motor load switch P kW
220/230 V P kW 4
230 V Star-delta P kW 4
400 V P kW 5.5
400 V Star-delta P kW 5.5
500 V P kW 5.5
500 V Star-delta P kW 7.5
690 V P kW 5.5
690 V Star-delta P kW 5.5
AC-23A Motor load switches (main switches maintenance switches) P kW