Datasheet

03/20/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 8
MOTOR�PROTECTION,START.PKZM0
Part�no. PKZM0-0,4
Article�no. 072732
as a 690VAC voltmeter protective device
Program
Product range PKZM0 motor protective circuit-breakers up to 32 A
Basic function Motor protection
Connection technique Screw terminals
Contact sequence
220 - 240 V
AC-3
220 V 230 V 240 V P kW 0.06
380 V 400 V 415 V P kW 0.09
440 V P kW 0.12
500 V P kW 0.12
660 V 690 V P kW 0.18
Rated uninterrupted current I
u
A 0.4
Setting�range
Overload releases I
r
A 0.25 - 0.4
Short-circuit releases
max. I
rm
A 5.6
Notes
Phase failure sensitivity to IEC/EN 60947-4-1, VDE 0660 part 102.
Can be snap-fit to IEC/EN 60715 top-hat rail with 7.5 or 15mm height
PTB 10 ATEX 3013, see manual
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No. E36332
UL CCN NLRV
CSA File No. 12528
CSA Class No. 3211-05
NA Certification UL listed, CSA certified
Specially designed for NA No
Suitable for Branch circuit: Manual type E if used with terminal, or suitable for group installations
General
Standards IEC/EN 60947, VDE 0660
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Storage °C - 25 - 80
Open °C - 25 - 55
Enclosed °C - 25 - 40

Summary of content (8 pages)