Datasheet

03/22/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 3
AUXILIARY�SWITCH�NHI-PKZ0
Part�no. NHI-E-10-PKZ0
Article�no. 082884
For motor-protective circuit-breakers
Program
Contacts
N/O = Normally open 1 N/O
Contact diagram
Contact sequence
Connection technique Screw terminals
For use with PKZM01
PKZM0
PKZM4
PKZM0-T
PKM0
PKE
Notes
Can be retrofitted to motor-protective circuit-breakers, transformer-protective circuit-breakers, motor-protective circuit-breakers for starter combinations from serial number
01.
45 mm (PKZM0 and PKZM01) or 55 mm (PKZM4) widths of the motor-protective circuit-breakers remain unchanged.
NHI-E...-PKZ0-C not usable for MSC...-type motor starter combinations.
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
UL File No. E36332
UL CCN NLRV
CSA File No. 12528
CSA Class No. 3211-05
NA Certification UL listed, CSA certified
Specially designed for NA No
Auxiliary�contacts
Rated impulse withstand voltage U
imp
V
AC
4000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V
U
e
V
AC
400
U
e
V
DC
250
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts V
AC
690
Rated operational current I
e
A
AC-15
220 - 240 V I
e
A 1
DC-13 L/R - 100 ms
24 V I
e
A 2
60 V I
e
A 1
110 V I
e
A 0.5
Lifespan S
Lifespan, mechanical Operations x
10
6
> 0.1
Lifespan, electrical Operations x
10
6
0.1

Summary of content (3 pages)