Datasheet

05/22/2017 102087 - HPL-ED2017 V32.0 EN 1 / 4
Over�current�switch,�10A,�1p,�C-Char,�AC
Part�no. FAZ-C10/1-NA
Article�no. 102087
Catalog�No. FAZ-C10/1-NA
Similar to illustration
Delivery�program
Basic function Miniature circuit-breakers
Number of poles 1 pole
Tripping characteristic C
Application Switchgear for export to North America (UL-listed)
Rated current I
n
A 10
Rated switching capacity acc. to IEC/EN 60947-2 kA 15
Product range FAZ-NA
Technical�data
Electrical
Standards UL 489, CSA C22.2 No. 5
IEC 60947-2
Rated operational voltage U
e
V
U
e
V AC 277/480 Y
V DC 60
Rated switching capacity acc. to IEC/EN 60947-2 kA 15
Characteristic B, C, D
Selectivity Class 3
Lifespan Operations > 20000
Direction of incoming supply as required
Mechanical
Standard front dimension mm 45
Enclosure height mm 105
Terminal protection Finger and back-of-hand proof to BGV A2
Mounting width per pole mm 17.7
Mounting IEC/EN 60715 top-hat rail
Degree of Protection IP20, IP40 (when fitted)
Terminals top and bottom Twin-purpose terminals
Mounting position As required
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 10
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 1.8
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 75
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification

Summary of content (4 pages)