1
Rated operational current: Making and breaking conditions to DC-13, L/R constant as stated.
Description
XTOB … CC1
Specification
XTOB … DC1
Specification
Auxiliary and Control Circuit Connections
Impulse withstand voltage (U
imp
) Vac 6000 6000
Overvoltage category/pollution degree III/3 III/3
Terminal capacity
Solid, mm
2
2 x (0.75–4) 2 x (0.75–4)
Flexible with ferrule, mm
2
2 x (0.75–2.5) 2 x (0.75–2.5)
Solid or stranded, AWG 2 x (18–12) 2 x (18–12)
Terminal screw M3.5 M3.5
Tightening torque Nm (lb-in) 0.8–1.3 (7–11.5) 0.8–1.3 (7–11.5)
Tools
Pozidrive screwdriver Size 2 Size 2
Standard screwdriver 1 x 6 1 x 6
Auxiliary circuit rated insulation voltage (U
i
) Vac 500 500
Rated operational voltage (U
e
) Vac 500 500
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between the auxiliary contacts (Vac) 240 240
Conventional thermal current, I
th
66
Rated operational current—AC-15
NO contact
120V 1.5 1.5
240V 1.5 1.5
415V 0.5 0.5
500V 0.5 0.5
NC contact
120V 1.5 1.5
240V 1.5 1.5
415V 0.9 0.9
500V 0.8 0.8
Rated operational current—DC-13 L/R
<
15 ms
1
NO contact
24V 0.9 0.9
60V 0.75 0.75
110V 0.4 0.4
220V 0.2 0.2
Short-circuit rating without welding maximum fuse, A gG/gL 6 6