Eaton® 9E UPS 20–30 kVA (208/220V) Installation and Operation Manual
Eaton® 9E UPS 20–30 kVA (208/220V) Installation and Operation Manual
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
Table of Contents 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 1-2 1-2 1-2 1-2 1-2 1-2 1-2 1-2 1-2 1-3 1-3 1-3 1-3 1-3 1-3 1-4 1-4 1-4 1-4 1-4 1-4 1-5 1-5 1-6 1-6 SAFETY WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 1.2 1.3 1.
Table of Contents 4.7 4.8 4.9 4.10 4.11 Integrated Accessory Cabinet-Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Accessory Cabinet-Tie and Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Accessory Cabinet-Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Power Wiring Installation .
Table of Contents 6.3.12 Using the UPS LOAD OFF Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.3.13 Using the Remote Emergency Power-off Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4 Multiple UPS Parallel Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.4.
Table of Contents This page intentionally left blank. iv Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
List of Figures Figure 1-1. Figure 3-1. Figure 3-2. Figure 3-3. Figure 3-4. Figure 3-5. Figure 4-1. Figure 4-2. Figure 4-3. Figure 4-4. Figure 4-5. Figure 4-6. Figure 4-7. Figure 4-8. Figure 4-9. Figure 4-10. Figure 4-11. Figure 4-12. Figure 4-13. Figure 4-14. Figure 4-15. Figure 4-16. Figure 4-18. Figure 4-19. Figure 4-20. Figure 4-21. Figure 4-22. Figure 4-23. Figure 4-24. Figure 5-1. Figure 5-2. Figure 5-3. Figure 5-4. Figure 5-5. Figure 5-6. Figure 6-1. Figure 6-2. Figure 6-3. Figure 6-8. Figure 6-9.
List of Figures This page intentionally left blank. vi Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
List of Tables Table 3-1. Table 3-2. Table 3-3. Table 3-4. Table 3-5. Table 3-6. Table 3-7. Table 3-8. Table 3-9. Table 4-1. Table 4-2. Table 4-3. Table 4-4. Table 4-5. Table 6-1. Table 6-2. Table 6-3. Table 6-4. Table 6-5. UPS Cabinet Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UPS Cabinet Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of Tables This page intentionally left blank. viii Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
Chapter 1 Introduction The Eaton® 9E 20–30 kVA uninterruptible power supply (UPS) is a true online, continuous-duty, transformerless, double-conversion, solid-state, three-phase system, providing conditioned and uninterruptible AC power to protect the customer's load from power failures.
Introduction 1.1 UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power protection. The descriptions in this section provide a brief overview of the UPS standard features. 1.1.1 Installation Features Power wiring can be routed to the back of the cabinet with connections made to easily accessible terminals. Control wiring is routed through the top of the cabinet and must be installed in accordance with Class 1 wiring methods. 1.1.
Introduction 1.2.3 Integrated Transformer Cabinet An single transformer Integrated Transformer Cabinet (ITC) provides three-phase 480 Vac input to three-phase 208Y/120 Vac output voltage transformation and isolation for input to the Eaton 9E UPS. An optional Dual transformer ITC adds three-phase 208 Vac input to three-phase 480Y/277 Vac output voltage transformation and isolation for output to the critical load.
Introduction 1.2.9 Monitoring and Communication Mini-Slot Cards – Optional Mini-Slot® cards support several protocols, such as SNMP, HTTP, Modbus® and RS232. See Chapter 7, “Communication,“ for additional information on monitoring and communication features. 1.2.10 Dual Feed Optional dual-feed input terminals are available to provide a separate bypass feed to the UPS. 1.2.
Introduction 1.6 Conventions Used in This Manual This manual uses these type conventions: l Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or represents a command or option that you type or enter at a prompt. l Italic type highlights notes and new terms where they are defined. l Screen type represents information that appears on the screen or LCD. Icon Description Note Information notes call attention to important features or instructions.
Introduction 1.
Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Read all instructions before operating the equipment and save this manual for future reference. The UPS is designed for industrial or computer room applications, and contains safety shields behind the door and front panels.
Safety Warnings l Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contacting any part of a grounded battery can cause a risk of electric shock. An electric shock is less likely if you disconnect the grounding connection before you work on the batteries. l Proper disposal of batteries is required. Refer to local codes for disposal requirements. l Do not dispose of batteries in a fire. Batteries may explode when exposed to flame.
Section 1 Installation
Chapter 3 UPS Installation Plan and Unpacking Use the following basic sequence of steps to install the UPS: 3.1 1. Create an installation plan for the UPS system (Chapter 3). 2. Prepare your site for the UPS system (Chapter 3). 3. Inspect and unpack the UPS cabinet (Chapter 3). 4. Unload and install the UPS cabinet, and wire the system (Chapter 4). 5. Install features, accessories, or options, as applicable (Chapter 4). 6. Complete the Installation Checklist (Chapter 4). 7.
UPS Installation Plan and Unpacking Table 3-1.
UPS Installation Plan and Unpacking Back Dimensions are in millimeters [inches] Front Right Side Figure 3-1. UPS Cabinet Dimensions (Front and Right Side Views) Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS Installation Plan and Unpacking Front Front Top Bottom Dimensions are in millimeters [inches] Figure 3-2. UPS Cabinet Dimensions (Top and Bottom Views) 3-4 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS Installation Plan and Unpacking CG Weight and Center of Gravity A With Batteries (9E–20 – 4 strings) 517 (20.4) B C Weight kg (lb) 259 [10.20] 399 [15.71] 377 (831) With Batteries (9E–30/20 and 9E–30/30 – 6 strings) 477 [17.60] 259 [10.20] 399 [15.71] 476 (1049) Without Batteries 197 (434) 657 [25.87] 249 [9.80] 399 [15.71] Dimensions are in millimeters [inches] Figure 3-3.
UPS Installation Plan and Unpacking 0.87 [0.22] 115.8 [4.56] 88.9 [3.50] 114.3 [4.50] 95.3 [3.57] (Square) 1.57 [0.40] Needed to remove key Front View 1/2" Knockout Pattern (Typical 5 Sides Dimensions are in millimeters [inches] Figure 3-4. Remote EPO Switch Dimensions 3.2.2 UPS System Power Wiring Preparation Read and understand the following notes while planning and performing the installation: WARNING As a result of the connected loads high leakage current is possible.
UPS Installation Plan and Unpacking l l The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses four wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment operation. Parallel UPS input wiring size requirements and output wiring size requirements from the UPSs to the Integrated Accessory Cabinet-Tie (IAC-T) or Integrated Accessory Cabinet-Tie and Bypass (IAC-TB) are the same as listed in Table 3-4.
UPS Installation Plan and Unpacking The power wiring terminals are pressure terminations, UL and CSA rated at 90°C. See Table 3-5 for external power cable terminations. Figure 4-7 and Figure 4-8 show the location of the UPS power cable terminals. Table 3-5.
UPS Installation Plan and Unpacking Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-6 for conduit requirements. Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors. Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground conductor sized in accordance with NEC Table 250.122.
UPS Installation Plan and Unpacking The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values for AC output to critical load shown in Table 3-4. The recommended line-to-line load unbalance is 50% or less. Bypass and output overcurrent protection and bypass and output disconnect switches are to be supplied by the customer. Table 3-8 lists the recommended rating for bypass and output circuit breakers. Table 3-8.
UPS Installation Plan and Unpacking LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by the customer. l The REPO feature opens all relays in the UPS cabinet and isolates power from your critical load. Local electrical codes may also require tripping upstream protective devices to the UPS. l The REPO switch must be a latching-type switch not tied to any other circuits.
UPS Installation Plan and Unpacking 2. Use a forklift or pallet jack to move the packaged cabinet to the installation site, or as close as possible, before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks between the supports on the bottom of the pallet (see Figure 3-3 for the UPS cabinet center of gravity measurements). CAUTION Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over. 3.
UPS Installation Plan and Unpacking Figure 3-5. UPS Cabinet as Shipped on Pallet (wood container removed) Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS Installation Plan and Unpacking This page intentionally left blank. 3-14 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
Chapter 4 4.1 UPS System Installation Preliminary Installation Information WARNING Installation should be performed only by qualified personnel. Refer to the following while installing the UPS system: 4.2 l Chapter 3 for cabinet dimensions, equipment weight, wiring and terminal data, and installation notes. l Do not tilt the cabinets more than ±10 during installation. l If perforated floor tiles are required for ventilation, place them in front of the UPS.
UPS System Installation Front Door Shipping Bracket Bolts Pallet Shipping Bracket Bolts Front Shipping Bracket Figure 4-1. Removing the Front Shipping Bracket 5. Remove four bolts securing the rear shipping bracket to the cabinet and four bolts securing the bracket to the pallet (see Figure 4-3). Remove the rear shipping bracket. If installing the cabinet permanently, retain the shipping bracket and securing hardware for later use.
UPS System Installation 10. If permanently mounting the system, proceed to Step 11; otherwise, continue to Step 13. 11. Using the retained hardware, reinstall the shipping brackets removed in Step 2 and Step 5 to the front and rear of the UPS cabinet with the angle facing outward (see Figure 4-1 and Figure 4-3). 12. Secure the cabinet to the floor with customer-supplied hardware. 13. Proceed to paragraph 4.3.
UPS System Installation Shipping Bracket Bolts Pallet Shipping Bracket Bolts Rear Shipping Bracket Figure 4-3. Removing the Rear Shipping Bracket 4-4 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation Figure 4-4. Rolling the Cabinet Down the Ramp Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation 4.3 Installing Power Terminal Cover Base NOTE Wiring can be installed between the UPS and accessory cabinets by using conduit or by routing wiring through the power terminal cover base wiring channels. To install the Power Terminal Cover Base: 1. Locate the terminal cover base (see Figure 4-5) from the parts kit. 2. If installing wiring using conduit, proceed to Step 3; otherwise, proceed to Step 4. 3.
UPS System Installation Power Terminal Cover Base Installed Conduit Landing for AC Input, Output, and Bypass, DC Input, and REPO. (Install conduit to bottom of plate.) Back Figure 4-6. UPS Power Terminal Cover Base Installation and Conduit Landing Wire Entry Locations 4.4 External Battery Cabinet Installation If installing External Battery Cabinets (EBCs), refer to the Eaton 9E External Battery Cabinet Installation Manual listed in paragraph 1.8 for installation instructions.
UPS System Installation 4.6 Integrated Accessory Cabinet-Bypass Installation If installing an IAC-B, refer to the Eaton 9E Integrated Accessory Cabinet-Tie and Bypass Installation and Operation Manual listed in paragraph 1.8 for installation instructions. After the IAC-B is installed, proceed to paragraph 4.9 if installing Integrated Accessory Cabinet-Distribution; otherwise, proceed to paragraph 4.10 to complete the wiring of the UPS. 4.
UPS System Installation WARNING As a result of the connected loads high leakage current is possible. Connection to earth ground is required for safety and proper product operation. Do not check UPS operation by any action that includes removal of the earth (ground) connection with loads attached. 7. Ground the UPS according to local and/or national electrical wiring codes by routing and connecting the ground wire to the input ground lug. See Figure 4-7 for UPS terminal locations.
UPS System Installation Ground Terminals DC Input from External Battery + Neutral (N) Phase C (L3) Phase B (L2) Phase A (L1) DC Input from External Battery - Phase A (L1) AC Input to UPS Rectifier Phase B (L2) Phase C (L3) Neutral (N) Phase C (L3) Phase B (L2) Neutral (N) Phase A (L1) AC Input to UPS Bypass Figure 4-8. Power Terminal Detail 4-10 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation Power Terminal Cover Right Side Installed Power Terminal Cover Top Installed Power Terminal Cover Left Side Installed Back Figure 4-9. Power Terminal Cover Top Installation Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation 4.11 Installing Interface Wiring and Connections 4.11.1 Installing Building Alarm Wiring and Connections To install wiring: 1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, “UPS Operating Instructions,“ for shutdown instructions. 2. To locate the appropriate terminals and review the wiring and termination requirements, see paragraph 3.2.3, Table 4-1, Figure 4-10, Figure 4-11, and Figure 4-12.
UPS System Installation Building Alarm (See Figure 4-12 for Detail) Mini-Slot Communication Bay 1 REPO Terminals (See Figure 4-19 for Detail) Mini-Slot Communication Bay 2 Pull Chain Terminals Parallel CAN Output (RJ45 Parallel CAN Input (RJ45) Figure 4-11. Interface Terminal Detail (Terminal Cover Removed) UPS Building Alarm 1 Building Alarm 3 Building Alarm 2 Figure 4-12. Building Alarm Terminal Block Connector Assignments Table 4-1. Building Alarm Connections Building Alarm Terminal 3.
UPS System Installation NOTE c. Remove the screws securing the top rear panel (see Figure 4-10). Supporting the panel, tilt the panel away from the cabinet and disconnect the fan connector from the wiring harness. d. Remove the panel. Retain the panel and hardware for later use. e. Remove the interface terminal cover (see Figure 4-13). Retain the cover and hardware for later use. NOTE 4-14 The lower fan is attached to the top rear panel.
UPS System Installation Interface Terminal Cover Installed Interface Terminal Cover Figure 4-13. Interface Terminal Cover Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation Wiring Access Interface Wiring Channel Zip Tie Mounting Clips (4 places) Interface conduit landing area Power Terminal Cover Base Figure 4-14. Interface Conduit Landing and Wiring Channel Wiring Access Figure 4-15. Interface Wiring Access 4-16 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation 4.11.2 Installing Parallel Pull Chain and CAN Control Wiring and Connections To install wiring: 1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, “UPS Operating Instructions,“ for shutdown instructions. 2. To locate the appropriate terminals and review the wiring and termination requirements, see paragraph 3.2.3, Table 4-2, Figure 4-10, Figure 4-11, and Figure 4-16. UPS Pull Chain Figure 4-16.
UPS System Installation k. Install the power terminal cover right and left sides using the provided hardware. 4. Route and install RJ-45 Controller Area Network (CAN) cables between the UPS cabinets. See Figure Figure 4-11 and Figure 4-17 for wiring information. 5. Route and install pull chain wiring between the UPS cabinets and cabinet MOBs. See Figure 4-11, Figure 4-16, and Figure 4-17 for wiring information. 6. Reinstall the interface terminal cover using the retained hardware. 7.
COM NO 1 3 CUSTOMER TERMINAL BLOCK CONNECTIONS NC 2 M O B 1 BUILDING ALARM CN9 1 2 COM 5 NO 4 6 NC 25 COM NO 7 9 NC 8 M O B 2 COM 11 NO 10 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 UPS 3 OUT CN6 CAN BUS COM NO 13 NC 15 14 M O B 3 COM 17 NO 16 NC 18 27 IN CN3 COM NO 19 NC 21 20 TERMINATING JUMPER M O B 4 COM 23 NO 22 TWISTED PAIRS NC 24 28 PULLCHAIN CN4 1 2 UPS 4 OUT CN6 CAN BUS BUILDING ALARM CN9 1 2 RJ-45 CABLE
UPS System Installation 4.12 Installing a REPO Switch A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the UPS and remove power to the critical load from a location away from where the UPS is installed. Figure 4-18 shows a REPO switch. NOTE 1 Before installing a REPO switch, verify that the UPS was installed according to the instructions in paragraphs 4.2 through 4.11.
UPS System Installation UPS Normally Closed REPO Contacts Normally Open REPO Contacts Figure 4-19. REPO Terminal Block Connector Assignments Table 4-3. REPO Connections REPO Terminal 1 2 3 4 4. Input: normally-closed dry contact used to activate UPS EPO from a remote switch. Input: normally-open dry contact used to activate UPS EPO from a remote switch. Route the REPO wiring to the terminal block: a. If not already removed, remove the power terminal cover right and left sides (see Figure 4-9).
UPS System Installation 6. If using a normally-closed REPO switch, connect a jumper wire between pins 3 and 4 on the REPO terminal block. 7. If you are installing multiple REPO switches, wire additional switches in parallel with the first REPO. 8. If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A second contact block is provided on the REPO switch for this function (see Figure 4-18).
UPS System Installation 1 REPO Switch (NC) 1 Twisted Wires 2 2 REPO TB 3 4 NOTE REPO switch rating is 24 Vdc, 1A minimum. NOTE The REPO switch must be a latching-type switch not tied to any other circuits. Figure 4-21. Normally-Closed REPO Switch Wiring 4.13 Connecting Internal Battery Strings DANGER This battery section contains its own energy source. Risk of electric shock. Do not touch uninsulated battery terminals. The internal wiring may carry LETHAL VOLTAGES.
UPS System Installation NOTE The Eaton 9E–20 model has battery strings installed on two shelves. The Eaton 9E–30/20 and Eaton 9E–30/30 models have battery strings installed on three shelves. 6. Repeat Step 3 through Step 5 for each battery shelf (see Figure 4-23) to complete the battery string connections. 7. Reinstall the internal safety shield panel removed in Step 2. 8. Close the outside door and secure the latch. Bottom Internal Safety Shield Panel (Batteries are located behind safety shield.
UPS System Installation Battery Trays Battery Shelf Battery Section Battery Strings NOTE The Eaton 9E–20 model has battery strings installed on two shelves. The Eaton 9E–30/20 and Eaton 9E–30/30 models have battery strings installed on three shelves. Figure 4-23. Battery Section Black Connector Red Connector White Flags Black Connectors Red Connectors Figure 4-24. Battery String Connections Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
UPS System Installation 4.14 Initial Startup Startup may be performed by the customer’s battery qualified electrical contractor for single (not parallel) UPS installations without any accessory cabinets such as an External Battery Cabinet. Startup and operational checks for parallel systems or installations with accessory cabinets must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms specified on page W-1 become void.
UPS System Installation Installation Checklist o All packing materials and restraints have been removed from each cabinet. o The UPS cabinet is placed in its installed location o All conduits and cables are properly routed to the UPS and any ancillary cabinets. o All power cables are properly sized and terminated. o Neutral conductors are installed. o A ground conductor is properly installed. o Building alarms are wired appropriately. (Optional) o LAN drops are installed.
UPS System Installation Notes ________________________________________________________________________ ________________________________________________________________________ ________________________________________________________________________ ________________________________________________________________________ ________________________________________________________________________ ________________________________________________________________________ __________________________________________
Section 2 Operation
Chapter 5 5.1 Understanding UPS Operation UPS System Overview The Eaton 9E UPS is a continuous-duty, solid-state, transformerless, three-phase, true online system that provides conditioned and uninterruptible AC power to the UPS system's output and critical load. The basic system consists of a rectifier, battery converter, inverter, monitoring/operation control panel, integrated communication server, and digital signal processor (DSP) logic. Figure 5-1 shows the main elements of the UPS system.
Understanding UPS Operation 5.2 Single UPS A single UPS operates independently to support an applied load from the inverter, providing conditioned and uninterruptible AC power to the critical load from the output of the module. During an outage, the inverter continues to operate, supporting power to the load from the battery supply. If the unit requires service, applied loads are transferred to the internal bypass either automatically or manually.
Understanding UPS Operation If the utility AC power is interrupted or is out of specification, the UPS automatically switches to Battery mode to support the critical load without interruption. When utility power returns, the UPS returns to Normal mode.
Understanding UPS Operation 5.2.4 Bypass Mode CAUTION The critical load is not protected from voltage or frequency fluctuations or power outages while the UPS is in Bypass mode. The UPS automatically switches to Bypass mode if it detects an overload, load fault, or internal failure. The UPS can also be transferred from Normal mode to Bypass mode manually. The bypass source supplies the commercial AC power to the load directly.
Understanding UPS Operation 5.2.5 Battery Mode The UPS automatically transfers to Battery mode if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery provides emergency DC power that the inverter converts to AC power. Figure 5-4 shows the path of electrical power through the UPS system when operating in Battery mode.
Understanding UPS Operation 5.3 Single UPS Unit System Oneline Configurations The system oneline drawings in this section show the simplified internal structure of the UPS, battery supply, and basic maintenance bypass.
Understanding UPS Operation AC Input to UPS Rectifier 4 Wire A-B-C Rotation A L1, L2, L3, N Parallel CAN Pull Chain AC Input to Bypass 4 Wire A-B-C Rotation (optional) Mini-Slot Interface Remote EPO B L1, L2, L3, N Internal Single-Feed Jumper Interface Board Static Switch Input Breaker Backfeed Relay Fuse Input Relay Rectifier Inverter Output Relay Fuse L1, L2, L3, N D AC Output to Critical Load Battery Converter Battery Relay Fuse UPM 1 UPS CABINET NOTE Callout letters A, B, and D map
Understanding UPS Operation AC Input to UPS Rectifier 4 Wire A-B-C Rotation AC Input to Bypass 4 Wire A-B-C Rotation (optional) A B L1, L2, L3, N Pull Chain Parallel CAN Remote EPO Mini-Slot Interface L1, L2, L3, N Internal Single-Feed Jumper Interface Board Static Switch Input Breaker Backfeed Relay Fuse Input Relay Rectifier Inverter Output Relay Fuse L1, L2, L3, N Battery Converter Battery Relay Fuse UPM 1 C Battery Breaker EXTERNAL BATTERY CABINET NOTE Callout letters A, B, C, and D
Chapter 6 UPS Operating Instructions This section describes how to operate the UPS. 6.1 NOTE 1 Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has been performed by authorized service personnel. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the system operates properly.
UPS Operating Instructions Bypass Breaker (Optional) Input Breaker Maintenance Bypass Switch (Optional) Figure 6-2. UPS Breakers 6.1.1 Control Panel The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 6.2. 6.1.2 l l l 6-2 Circuit Breakers Input Circuit Breaker – The Input circuit breaker is used to control the AC input to the UPS rectifier.
UPS Operating Instructions 6.2 Using the Control Panel The following paragraphs describe the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel (see Figure 6-3) is located on the front door of the UPS. 2 3 1 Figure 6-3. UPS Control Panel The control panel consists of: l A liquid crystal display (LCD) (1) l Menu navigation pushbutton switches (2) l A vertical column of status indicators (3). See paragraph 6.2.1.
UPS Operating Instructions 6.2.2 System Events When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change from Normal mode. System events on the UPS can be indicated by horns, lights, messages, or all three. Select the EVENTS symbol from the menu bar on the main menu screen to display the active events screen.
UPS Operating Instructions 6.2.3 Using the LCD and Pushbuttons The LCD on the control panel provides an operator interface with the UPS system. Figure 6-4 identifies the display areas discussed in the following sections. Alarm: Output AC Under Voltage A B D C Meter Events History Controls Setup Figure 6-4. Parts of the LCD A The UPS status area automatically scrolls between the Eaton model number, current date and time, active alarms, UPS status, load percent, and battery runtime for the UPS.
UPS Operating Instructions 6.2.4 Using the Menu The UPS menu bar allows you to display data in the information area to help you monitor and control UPS operation. Table 6-2 shows the basic menu structure. Table 6-2. Display Function Menu Map Menu Option Description METERS Displays performance meters for the system or critical load. EVENTS Displays the list of Active System Events. HISTORY CONTROLS SETUP ESC Displays a historical log of system events. Displays the System Control screen.
UPS Operating Instructions 6.2.6 Display Menu Operation Table 6-3 describes the menu functions and how to use them. Table 6-3. Display Menu Operation Function Subfunction Meters – UPS Operation The Meter screens show the UPS meter readings for the unit. The default voltage displayed on these screens is phase-to-neutral. These can be changed to display the voltage phase-to-phase (A-B, B-C, C-A).
UPS Operating Instructions Table 6-3. Display Menu Operation Function Subfunction Operation Setup – Config (System Level 1 Setup) (continued) Set Date and Time MM/DD/YYYY The Set Date and Time MM/DD/YYYY screen allows the internal date and time of the UPS to be set in the month/day/year format. The date and time information is used for display on the screen and for logging events in the Event and History Logs. Use the LEFT or RIGHT arrow pushbutton to highlight the setting to be changed.
UPS Operating Instructions Status: Load Off Info About User Config Service Figure 6-6. Typical Initial Setup Screen 6.2.7 System Controls Select the CONTROLS symbol on the main menu bar, then press the RETURN pushbutton to display the Controls screen. Normal operation, transfer to bypass, load off, and charger control commands are controlled through this screen. In addition, the screen displays the current status of the UPS. Figure 6-7 shows the System Control screen.
UPS Operating Instructions Status: Load Off Load Off Normal Load Off Bypass HE : Enable Disable UPS Battery UPM Figure 6-7. Typical System Control Screen Table 6-4. Command Menu Operation Function Subfunction Operation UPS Control Commands Use the up or down arrow pushbutton to highlight the command function desired, then press the RETURN pushbutton to execute the command or proceed to further command screens.
UPS Operating Instructions 6.3 Single UPS Operation 6.3.1 NOTE 1 If an External Battery Cabinet (EBC) is installed, refer to the Eaton 9E External Battery Cabinet Installation Manual listed in paragraph 1.8 for EBC battery breaker location. NOTE 2 If an Integrated Transformer Cabinet (ITC) is installed, refer to the Eaton 9E Integrated Transformer Cabinet Installation Manual listed in paragraph 1.8 for ITC transformer breaker locations.
UPS Operating Instructions 17. If requested, enter the Level 1 password. Default password is 1111. The rectifier and inverter turn on. The inverter continues to ramp up to full voltage. Once the inverter reaches full voltage, the UPS output relay closes and the static switch turns off. Power is now supplied to the critical load in HE Normal mode. It takes approximately one minute for the UPS to achieve HE Normal mode. The Normal status indicator is illuminated. 18.
UPS Operating Instructions 6.3.3 Transfer from Normal to Bypass Mode To transfer the critical load to Bypass mode: CAUTION In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities. 1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. 2. If not already selected, select UPS on the System Control screen. 3. On the UPS System Control screen, select the NORMAL pushbutton.
UPS Operating Instructions 6.3.6 Transfer from Standard Normal Mode to HE Normal mode To transfer the load to HE Normal mode: 1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. 2. If not already selected, select UPS on the System Control screen. 3. On the UPS System Control screen, select the HE: DISABLE RETURN pushbutton. ENABLE command, then press the The UPS transfers to HE Normal mode if no abnormal power conditions are detected.
UPS Operating Instructions Interlock Switch Maintenance Bypass Switch with cover removed. Maintenance Bypass Switch with cover installed. Figure 6-8. Maintenance Bypass Switch 6.3.9 UPS and Critical Load Shutdown To perform maintenance or service on the critical load, shut down power to the load: 1. Turn off all equipment that is being powered by the UPS. 2. Perform the LOAD OFF procedure in paragraph 6.3.12. The output and bypass backfeed relays open, and the power module is turned off. 3.
UPS Operating Instructions 6.3.10 Charger Control To turn the battery charger on: 1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. 2. Select Battery on the System Control screen. 3. On the Battery System Control screen, select the RESTING RETURN pushbutton. CHARGING command, then press the To turn the battery charger off: 1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. 2.
UPS Operating Instructions CAUTION All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this feature only when you want to de-energize the critical load. 4. Select Yes or no, then press the RETURN pushbutton. Selecting Yes will immediately shut down the UPS and de-energize the critical load. Selecting No will abort the shutdown. CAUTION Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and cleared.
UPS Operating Instructions 2. To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate clockwise until the red pushbutton releases (see Figure 6-9). To remove the key, rotate the key back to the vertical position. 3. Restart the UPS by following the procedure in paragraph 6.3.1 or 6.3.2. WARNING Power is present inside the UPS cabinet after the upstream input feeder circuit breakers are opened because of the installed internal batteries.
UPS Operating Instructions 6.4 Multiple UPS Parallel Operation The paragraphs in this section provide operating instructions for a UPS system containing multiple UPSs. 6.4.1 NOTE 1 If an External Battery Cabinet (EBC) is installed, refer to the Eaton 9E External Battery Cabinet Installation Manual listed in paragraph 1.8 for EBC battery breaker location.
UPS Operating Instructions 16. If requested, enter the Level 1 password. Default password is 1111. All rectifiers and inverters turn on. The inverters continue to ramp up to full voltage. Once all inverters reaches full voltage, the UPS output relay closes and the static switches turns off. Power is now supplied to the critical load in HE Normal mode. It takes approximately one minute for the UPS to achieve HE Normal mode. The Normal status indicator is illuminated. 6.4.
UPS Operating Instructions 6.4.3 Transfer from Normal to Bypass Mode To transfer the critical load to Bypass mode: CAUTION In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities. 1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. 2. If not already selected, select UPS on the System Control screen. 3. On the UPS System Control screen, select the NORMAL pushbutton.
UPS Operating Instructions 6.4.6 Transfer from Standard Normal Mode to HE Normal mode To transfer the load to HE Normal mode: 1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed. 2. If not already selected, select UPS on the System Control screen. 3. On the UPS System Control screen, select the HE: DISABLE RETURN pushbutton. ENABLE command, then press the All of the UPSs transfer to HE Normal mode if no abnormal power conditions are detected.
UPS Operating Instructions 4. On the UPS System Control screen, select the NORMAL RETURN pushbutton. UPS OFF command, then press the The output and bypass backfeed relays open, and the power module is turned off on the UPS being shut down. Logic power remains on. WARNING Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened. 5. Open the UPS input and, if installed, the bypass feeder circuit breakers for the UPS being shut down. 6.
UPS Operating Instructions 4. Perform the battery charger off procedure in paragraph 6.4.12 for each UPS. The input and battery relays open. WARNING Power is present inside the UPS cabinets after the upstream input feeder circuit breakers are opened because of the installed internal batteries. 5. Open all of the UPS input circuit breakers. 6. If the UPSs contain a bypass breaker, open all of the bypass breakers. 7. Open all of the MOBs. 8.
UPS Operating Instructions 6.4.14 Using the UPS LOAD OFF Command A UPS Load Off is initiated by the Load Off command on the UPS Control screen. The UPS LOAD OFF controls the UPSs output by powering down the UPS and de-energizing the critical load. The UPSs (including Bypass) remains off until restarted. To use the LOAD OFF command: 1. Select the CONTROLS symbol on the main menu bar on the UPS to be shut down. The System Control screen is displayed. 2. Select UPS on the System Control screen. 3.
UPS Operating Instructions 6.4.15 Using the Remote Emergency Power-off Switch A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use this switch to control the UPS output. The REPO switch de-energizes the critical load and powers down the UPSs immediately, without asking for verification. The UPSs, including Bypass, remains off until restarted. CAUTION All power to the critical load is lost when the REPO switch is activated in the following step.
Chapter 7 Communication This chapter describes the communication features of the Eaton 9E UPS. For terminal wiring information, see paragraph 3.2.3 and paragraph 4.11. For location of the customer interface panel and terminals, see Figure 4-10 and Figure 4-11. 7.1 Mini-Slot Cards The Eaton 9E UPS has two standard, factory-installed Mini-Slot communication bays. See Figure 4-10 for bay locations.
Communication This page intentionally left blank. 7-2 Eaton 9E UPS (20–30 kVA, 208/220V) Installation and Operation Manual 164202124—Rev 5 www.eaton.
Chapter 8 UPS Maintenance The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This design allows authorized service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly.
UPS Maintenance 8.2 Performing Preventive Maintenance The UPS system requires very little preventive maintenance. However, the system should be inspected periodically to verify that the units are operating normally and that the batteries are in good condition. 8.2.1 DAILY Maintenance Perform the following steps daily: 1. Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the unit. 2.
UPS Maintenance Air Filter Figure 8-1. Air Filter Location 8.2.3 PERIODIC Maintenance Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit evidence of overheating. Particular attention should be given to the compression lug connections. Maintenance procedures should specify that the compression lug connections be retorqued to values listed in this manual. 8.2.
UPS Maintenance 8.3 Installing Batteries NOTE There is no manual DC disconnect device within the UPS. Install batteries in accordance with the battery and battery system manufacturer's instructions. 8.4 Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS. WARNING l l l Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required.
Chapter 9 9.1 Product Specifications Model Numbers The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in 50 or 60 Hz with various output power ratings. Models 9.2 Power Rating Frequency Eaton 9E–20 20 kVA 50/60 Hz Eaton 9E–30/20 20 kVA 50/60 Hz Eaton 9E–30/30 30 kVA 50/60 Hz Specifications The following sections detail the input, output, environmental, and battery specifications for the UPS. 9.2.
Product Specifications 9.2.2 UPS Output UPS Output Capacity 100% rated current Output Voltage Regulation ± 1% (10% to 100% load) Nominal Output Voltage 208 Vac and 220 Vac nominal 2% maximum THD (linear load) Output Voltage Harmonic Content 5% maximum THD (nonlinear load) Output Current See Table 3-4. Output Voltage Balance < 2% for 100% maximum load imbalance (linear load) Output Voltage Phase Displacement < 2.5 for 100% maximum load imbalance (linear load) Frequency Regulation 0.
Warranty LIMITED FACTORY WARRANTY FOR THREE-PHASE EATON® 9E UPS AND 9E UPS ACCESSORY PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, an Ohio Corporation (”Eaton”). LIMITED WARRANTY: This limited warranty (this ”Warranty”) applies only to the original end-user (the ”End-User”) of the Eaton Three-Phase 9E UPS and 9E UPS Accessory Products (the ”Product”) and cannot be transferred.
Warranty THIS WARRANTY IS THE ENDUSER'S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO OTHER, EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED). SOME STATES OR JURISDICTIONS DO NOT ALLOW THE EXCLUSION OF EXPRESS OR IMPLIED WARRANTIES, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU. IN THAT EVENT, SUCH WARRANTIES ARE LIMITED IN DURATION TO THE LIMITED WARRANTY PERIOD.
*164202124 5* 164202124 5