Data Sheet

DATASHEET - EASY-BOX-E4-AC1
Starter package consisting of EASY-E4-AC-12RC1, patch cable and
software license for easySoft
Part no. EASY-BOX-E4-AC1
Catalog No. 197229
Delivery program
Product range Control relays easyE4
Basic function Starter kit
Supply voltage 100 - 240 V AC, 100 - 240 V DC (cULus: 100 - 110 V DC)
Software EASYSOFT-SWLIC/easySoft 7
Technical data
General
Standards EN 61000-6-2
EN 61000-6-3
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-30
IEC 61131-2
EN 61010
EN 50178
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Terminal capacities
Solid
mm
2
0.2/4 (AWG 22 - 12)
Flexible with ferrule
mm
2
0.2/2.5 (AWG 22 - 12)
Standard screwdriver mm 0.8 x 3.5
Climatic environmental conditions
Operating ambient temperature °C -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
Condensation Take appropriate measures to prevent condensation
LCD display (clearly legible) °C 0 - 55
relative humidity % in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95
Air pressure (operation) hPa 795 - 1080
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations Hz In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms Impacts 18
Drop to IEC/EN 60068-2-31 Drop height mm 50
Free fall, packaged (IEC/EN 60068-2-32) m 1
Mounting position Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree III/2
Electrostatic discharge (ESD)
applied standard according to IEC EN 61000-4-2
Air discharge kV 8
Contact discharge kV 4
Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10
Insulation resistance
Clearance in air and creepage distances nach EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Insulation resistance per EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Back-up of real-time clock
Accuracy of real-time clock to inputs s/day typ. ± 2 (± 0.2 h⁄Year)
depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year)
are possible
01/09/2020 Eaton Y7-197229 ED2019 V63.0 EN 1 / 4