Data Sheet

DATASHEET - EMR6-I15-A-1
Overcurrent and undercurrent monitor, Current measuring range: 0.3 - 1.5
A, 1 - 5 A, 3 - 15 A, Supply voltage: 24 - 240 V AC, 50/60 Hz, 24 - 240 V DC
Part no. EMR6-I15-A-1
Catalog No. 184754
Alternate Catalog
No.
EMR6-I15-A-1
EL-Nummer
(Norway)
4101950
Delivery program
Product range EMR Measuring and monitoring relays
Basic function Current monitoring relays
Monitoring of single-phase DC and AC networks
On delay: None = 0 or adjustable from 0.1 to 30 s
Extension of the measurement range possible with current transformers
Monitoring of Overcurrent
Undercurrent
Current measuring range I∼/I= A 0.3 - 1.5 A
1 - 5 A
3 - 15 A
Contact sequence
Supply voltage 24 - 240 V AC, 50/60 Hz
24 - 240 V DC
Width mm 22.5
Technical data
General
Standards UL 508, CAN/CSA C22.2 No.14, GL, EAC, CCC, RMRS
Lifespan, mechanical Operations
x 10
6
30
Climatic proofing Damp heat, cyclical to IEC 60068-2-30: 24 h cycle, 55° C, 93% relative humidity, 96 h
Ambient temperature
Operation °C
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C + 60
Storage °C - 40 - 85
Mounting position As required
Shock resistance Class 2
Degree of protection
Terminals IP20
Enclosures IP50
Terminal capacities
mm
2
Solid
mm
2
1 x 0.5-2.5 (1 x 18-14 AWG)
Flexible with ferrule
mm
2
2 x 0.5-1.5 (2 x 18-16 AWG)
Standard screwdriver mm 4 x 0.8
Tightening torque Nm 0.6 - 0.8
Fixing Snap fixing, top-hat rail IEC/EN 60715
MTBF (mean time between failures) 382467 h
Contacts
Rated impulse withstand voltage U
imp
V AC 4000
Overvoltage category/pollution degree III/3
Power supply
Supply voltage 24 - 240 V AC, 50/60 Hz
24 - 240 V DC
Voltage tolerance x U
c
0.85 - 1.1
06/18/2021 Eaton 184754 ED2021 V80.0 EN 1 / 3