Data Sheet

DATASHEET - DE1-343D6FN-N20N
Variable speed starter, Rated operational voltage 400 V AC, 3-phase, Ie 3.6
A, 1.5 kW, 2 HP, Radio interference suppression filter
Part no. DE1-343D6FN-N20N
Catalog No. 174335
Alternate Catalog
No.
DE1-343D6FN-N20N
EL-Nummer
(Norway)
4110099
Delivery program
Product range Variable speed starter
Part group reference (e.g. DIL) DE1
Rated operational voltage U
e
400 V AC, 3-phase
480 V AC, 3-phase
Output voltage with V
e
U
2
400 V AC, 3-phase
480 V AC, 3-phase
Mains voltage (50/60Hz) U
LN
V 380 (-10%) - 480 (+10%)
Rated operational current
At 150% overload I
e
A 3.6
Note Rated operational current at an operating frequency of 16 kHz and an ambient air
temperature of +50°C
Assigned motor rating
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm
-1
at 50 Hz or 1800 min
-1
at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 400 V, 50 Hz
150 % Overload P kW 1.5
150 % Overload I
M
A 3.6
Note at 440 - 480 V, 60 Hz
150 % Overload P HP 2
150 % Overload I
M
A 3.4
Degree of Protection IP20/NEMA0
Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU
Fitted with Radio interference suppression filter
Parameterization Keypad
Fieldbus
drivesConnect
drivesConnect mobile (App)
Frame size FS1
Connection to SmartWire-DT yes
in conjunction with DX-NET-SWD3 SmartWire DT module
Technical data
General
Standards Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications CE, UL, cUL, RCM
Production quality RoHS, ISO 9001
Climatic proofing ρ
w
% < 95%, average relative humidity (RH), non-condensing, non-corrosive
Ambient temperature
Operating ambient temperature min. °C -10
Operating ambient temperature max. °C + 60
Derating between 50°C and 60 °C:
None if f
PWM
≦16kHz
None if I
e
≦3.2A
06/16/2021 Eaton 174335 ED2021 V80.0 EN 1 / 6