DATASHEET - PKZM0-10-T
Transformer-protective circuit-breaker, 3p, Ir=6.3-10A, screw connection
Part no. PKZM0-10-T
Catalog No. 088916
Alternate Catalog
No.
XTPT010BC1NL
EL-Nummer
(Norway)
4315159
Delivery program
Product range PKZM0...T transformer-protective circuit-breakers up to 25 A
Basic function Transformer protection
Notes Also suitable for motors with efficiency class IE3.
Connection technique Screw terminals
Contact sequence
Rated uninterrupted current I
u
A 10
Setting range
Overload releases I
r
A 6.3 - 10
short-circuit release
max. I
rm
A 224
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Notes For the protection of transformers with a high inrush current.
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15mm height.
Technical data
General
Standards IEC/EN 60947, VDE 0660
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Storage °C - 40 - 80
Open °C -25 - +55
Enclosed °C - 25 - 40
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 25
Altitude m Max. 2000
Terminal capacity main cable