The following configuration options are provided on the right-side panel of the Shutdown page:
•Edit power source
• Edit shutdown configuration
• Edit advanced shutdown criteria
•Test access
• Test shutdown
NOTE: Check the settings for the UPS shutoff option to ensure the expected behavior: with the “UPS shutoff” option
enabled, the shutdown sequence test will lead to the full UPS shutdown (see Figure 15).
Figure 15. Test Shutdown Warning Message
• Run Battery test: Launch a battery test if the following conditions are true:
– Battery must be in rest mode.
– The load must be over 25%.
• Run UPS Upgrade Tool if the following conditions are true (see Figure 16):
– A power source has been set up in the software.
– The Dell UPS Upgrade Tool is installed on the operating system.
• Run UPS Logs Extraction Tool if the following conditions are true:
– A power source has been set up in the software.
– The Dell UPS Logs Extraction Tool is installed on the operating system.
– Communication with UPS through a serial connection.
– It is installed on a Windows Operating System in the list of supported OS.
NOTE: If the Dell UPS is connected through the USB or if the software is running on a Linux Operating System (not
supported by the “Dell UPS Logs Extraction Tool,” the button will be disabled.