Setup Guide

Power requirements for PowerStore X model and PowerStore T
model
Power requirements will vary depending on system configuration, loading, and environmental conditions. The table below
describes the maximum expected power draw. To estimate power consumption values for your specific environment, go to
https://powercalculator.emc.com/.
Table 4. Power requirements
Requirement 1000T/ 1000X 3000T/3000X 5000T 5000X 7000T/7000X 9000T/9000X
Maximum input
power
240 VAC ± 10%, single phase
For 100-120V, a customer-supplied step-up transformer is required
AC Line Current
(operating
maximum at 200
VAC)
8.1 A 8.1 A 9.0 A 9.0 A 9.3 A 10.4 A
Power
Consumption
(operating
maximum at 200
VAC)
1629.6 VA (1597
W)
1629.6 VA (1597
W)
1792.9 VA (1757
W)
1792.9 VA (1757
W)
1868.4 VA (1831
W)
2088.8 VA
(2047 W)
Heat Dissipation
(operating
maximum)
5.74 x 10
6
J/hr,
(5,449 Btu/hr)
5.74 x 10
6
J/hr,
(5,449 Btu/hr)
6.32 x 10
6
J/hr,
(5,995 Btu/hr)
6.32 x 10
6
J/hr,
(5,995 Btu/hr)
6.59 x 10
6
J/hr,
(6,248 Btu/hr)
7.37 x 10
6
J/hr,
(6,985 Btu/hr)
AC Inlet type IEC320-C14 or IEC320-C20 appliance coupler per
power zone
IEC320-C20 appliance coupler per power zone
Normal input
frequency
47 Hz63 Hz
Maximum inrush
current
45 Apk "cold" per line cord at any line voltage
AC protection 20 A fuse on each power supply, single line
Ride-through
time
10 ms min
Current sharing ± 5 percent of full load, between power supplies
Startup Surge
Current
120 Apk "hot" per line cord, at any line voltage
Table 5. High ambient temperature shutdown
Ambient temperature Hardware fault Consequence
Above 45° C (113° F) None Non-critical warning generated .
Above 50° C (122° F) None Critical alert generated. System
shuts down after five minute timer
expires. If the temperature returns
to less than 45° C (113° F) , the
system powers on..
Any Three hottest drives have average temperature of
50° C (122° F)
System shuts down after five
minute timer expires.
Any Two fans fault System shuts down after five
minute timer expires.
Site planning 11