Table 18. High ambient temperature shutdown (continued)
Ambient temperature Hardware fault Consequence
to less than 45° C (113° F) , the
system powers on..
Any Three hottest drives have average temperature of
50° C (122° F)
System shuts down after five
minute timer expires.
Any Two fans fault System shuts down after five
minute timer expires.
Operating limits
Table 19. Operating limits
Description Limit
Temperature 5°C through 35°C normal, 35°C through
40°C for 10% of the time
Humidity -12°C DP and 8% to 85% RH (non-
condensing)
Temperature Gradient (disk) 20°C/hr
Altitude Compensation Normal: Lower temp 1°C per 300 M above
950 M
Improbable: Lower temp 1°C per 175 M
above 950 M
Shipping and storage requirements
NOTE:
Systems and components must not experience changes in temperature and humidity that are likely to cause
condensation to form on or in that system or component. Do not exceed the shipping and storage temperature gradient of
45°F/hr (25°C/hr).
Table 20. Shipping and storage requirements
Requirement Description
Ambient temperature -40° F to 149°F (-40°C to 65°C)
Temperature gradient 45°F/hr (25°C/hr)
Relative humidity 10% to 90% noncondensing
Elevation -50 to 35,000 ft (-16 to 10,600 m)
Storage time (unpowered) Recommendation Do not exceed 6 consecutive months of
unpowered storage.
Base enclosure airflow
The base enclosure uses an adaptive cooling algorithm that increases or decreases fan speed as the unit senses changes to the
external ambient temperature. Exhaust increases with ambient temperature and fan speed, and is roughly linear within
recommended operating parameters. Note that the information in the table below is typical, and was measured without cabinet
front/rear doors that would potentially reduce front-to-back air flow.