Manual

2 Dell Metered Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
OUTLETS The Rack PDU has twelve (12) 5-15 R outlets.
P
OWER CORD The Rack PDU has an IEC-320-C20 inlet and can be used with a detachable power cord (not provided).
J519N
Electrical
Input connection IEC-320-C20
Acceptable input voltage 100–120 VAC
± 10%
Maximum input current (phase) 16 A
Input frequency 50/60 Hz
Input power 1.9 kVA UL and C-UL (derated), PSE
Output voltage 100–120 VAC (Line-to-Neutral)
Output connections Twelve (12) 5-15 R
Maximum output current (outlet) 5-15 R: 12 A UL and C-UL (derated), PSE
Maximum output current (phase) 16 A UL and C-UL (derated), PSE
Physical
Dimensions
(H x W x D)
85.2 x 5.5 x 4.1 cm
(33.6 x 2.2 x 1.6 in)
Shipping dimensions
(H x W x D)
108.2 x 22.0 x 12.1 cm
(42.6 x 8.65 x 4.75 in)
Weight 2.0 kg (4.5 lb)
Shipping weight 3.2 kg (7.0 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing
Compliance
Safety UL, C-UL, PSE
EMC FCC Part 15 Class A, ICES-003 Class A, VCCI-A,
EN 55022 Class A, EN 55024, EN 61000-3-2,
EN 61000-3-3, AS/NZS CISPR 22 Class A,
EU EMC DIRECTIVE 2004/108/EC–latest revision
Environmental Dell 6T198