User's Manual

omconfig: Managing Components Using the Instrumentation Service 113
NOTE: This command is applicable to select Dell xx0xsystems that support PMBus
only.
Default Warning Thresholds
NOTE: Sensor managing capabilities vary across systems.
If you want to set both the upper and lower power consumption probe
warning threshold values to the recommended default value, type:
omconfig chassis pwrmonitoring config=probe index=
0 warnthresh=settodefault
or
omconfig mainsystem pwrmonitoring config=probe
index=0 warnthresh=settodefault
You cannot default one value and set another. If you default the minimum
warning threshold value, you are also selecting the default value for the
maximum warning threshold value.
Table 4-10. omconfig chassis pwrmonitoring/omconfig mainsystem pwrmonitoring
name=value pair 1 name=value pair 2 Description
index=<n> NA Number of the probe or probe index
(must be specified).
config=probe warnthresh=
settodefault
Sets minimum and maximum
warning thresholds values to default.
warnthresh=<n> Sets a value for the warning
threshold.
unit=watt | btuphr | watt: Displays the unit in Watts.
btuphr: Displays the unit in BTU/hr.
config=resetreading type=energy |
peakpower
energy: Resets the system energy
reading.
peakpower: Resets the system peak
power.